3
85198A_Manual of Electrical Installation for Pressure Probes KH-SIL2-Mobyle-series_07-2019_ENG
Electrical connections
The interface with SRP/CS (Safety Related Part of a Control System) is made by mean of multipolar connectors showed
on pictures below, where the connections are specified in case of amplified voltage output (3 wire) or current output (2
wire system, the sensor is connected in series with the current loop).
Interfaces with SRP/CS and voltage devices
RATIOMETRIC AND VOLTAGE AMPLIFIED OUTPUT
CURRENT AMPLIFIED OUTPUT – mod. E
Red
Black
Red
Black
White
OUTPUT
POWER SUPPLY
SIGNAL
POWER SUPPLY
2 1
3 4
G – Deutsch DT04-4P
Z - M12 x 1 (4 pin)
S – AMP Superseal 1.5
E - EN 175301-803
K – Metri-Pack 150
Protection IP67
Protection IP67
Protection IP67
Protection IP67
Protection IP65
LOAD DIAGRAM
(Current output)
F – 3 pole cable
Shield
White
Red
Black
Protection IP65
Ω
TO
TA
L
LOAD RESIST
ANCE RL
Operating
Area
POWER SUPPLY VOLTAGE
RL = < (Vsupply - 10V) / 0.02A