65
80415F_MSW_GFX4-IR_05-2019_ENG
Virtual instrument control is activated by means of parameter hd.1.
By setting parameters S.In and S.Ou you can enable the writing of some parameters via serial line, set the value of
inputs and the state of outputs.
You have to enable alarm setpoints AL1, ..., AL4 when write operations are continuous, and you don’t have to keep
the last value in eeprom.
Enabling the PV input means being able to exclude the local Tc or RTD acquisition and replace it with the value written
in the register VALUE_F.
Enabling digital input IN lets you set the state of this input, for example to run MAN/AUTO switching with the writing
of bit 7 in the register V_IN_OUT.
Likewise, you can set the on/off state of outputs OUT1, ..., OUT10 and of the LEDs by writing bits in the register
V_IN_OUT.
191
hd.1
R/W
Enable multiset
instrument control via serial
0
Table for multiset/ virtual instrument
Enable Enable
Multiset
virtual instrument
0
1
X
2
X
3
X
X
VIRTUAL INSTRUMENT CONTROL
224
s.In
R/W
Control inputs from serial
0 ... 255
0
Inputs InTA In.2 - In.1 AL4 AL3 AL2 AL1
Bit 7 6 5 4 3 2 1 0
225
s.0v
R/W
Control outputs from serial
0 ... 1023
0
Outputs Out10 Out9 Out8 Out7 Out6 Out5 Out4 Out3 Out2 Out1
Bit 9 8 7 6 5 4 3 2 1 0
628
s.LI
R/W
Control LEDs and digital inputs from
serial
0 ... 1023
0
Input
LED
D2 D1 O4 O3 O2 O1 D2 D1 ER RN
Bit 9 8 7 6 5 4 3 2 1 0
Parameter
bit
Resource enabled
Address of
Format
Name of register
image register
S.In
0
Alarm setpoint AL1
341
word
AL1_RAM
1
Alarm setpoint AL2
342
word
AL2_RAM
2
Alarm setpoint AL3
343
word
AL3_RAM
3
Alarm setpoint AL4
321
word
AL4_RAM
4
Input In.1
347
word
VALUE_F
6
Input In.2
348
word
VALAUX_F
7
Input In.TA
685
word
VALTA_F
S.Ou
0
Output OUT 1
344
word, bit 0
V_IN_OUT
1
Output OUT 2
344
word, bit 1
V_IN_OUT
2
Output OUT 3
344
word, bit 2
V_IN_OUT
3
Output OUT 4
344
word, bit 3
V_IN_OUT
4
Output OUT 5 (relays)
344
word, bit 4
V_IN_OUT
4
Output OUT 5 (continuous)
639
word
SERIAL_OUT5C*
5
Output OUT 6 (relays)
344
word, bit 5
V_IN_OUT
5
Output OUT 6 (continuous)
640
word
SERIAL_OUT6C*
6
Output OUT 7 (relays)
344
word, bit 6
V_IN_OUT
6
Output OUT 7 (continuous)
641
word
SERIAL_OUT7C*
7
Output OUT 8 (relays)
344
word, bit 7
V_IN_OUT
7
Output OUT 8 (continuous)
642
word
SERIAL_OUT8C*
8
Output OUT 9
344
word, bit 8
V_IN_OUT
9
Output OUT 10
344
word, bit 9
V_IN_OUT
S.LI
0
Led RN
351
word, bit 0
V_X_LEDS
1
Led ER
351
word, bit 1
V_X_LEDS
2
Led D1
351
word, bit 2
V_X_LEDS
3
Led D2
351
word, bit 3
V_X_LEDS
4
Led O1
351
word, bit 4
V_X_LEDS
5
Led O2
351
word, bit 5
V_X_LEDS
6
Led O3
351
word, bit 6
V_X_LEDS
7
Led O4
351
word, bit 7
V_X_LEDS
8
Input D1
344
word, bit 10
V_IN_OUT
9
Input D2
344
word, bit 11
V_IN_OUT
Table of virtual register addresses
* the value to be set is in the range 0...1000 if the corresponding rL.x is configured “0” or in the range 0...-1000 if the corresponding rL.x is configured “1”.
+16 For Heat/Cool control Ctr only: CT connected to cool output