64
80415F_MSW_GFX4-IR_05-2019_ENG
HETEROGENEOUS power control
Available only for Mod. 80 kW 57A full scale
This function matches that of a thermal cutout that disconnects the load based on instantaneous input.
The load is disconnected based on a preset priority.
Zone 1 has priority: in case of overload, zone 4 is disconnected, followed by zone 3, etc.
The maximum total controllable current in four zones for the 80 kW model is 160A.
The maximum current in a single zone is 57A.
Example: you can control three 50A loads and one 10A load without limits. With four 50A loads, if there is simultaneity,
the load connected to zone 4 is disconnected.
683
I.XET
R/W
Maximum current for heterogeneous
power control
0.0 ... 64.0 for GFX4 -IR 30 kW
0.0 ... 128.0 for GFX4-IR 60 kW
0.0 ... 160.0 for GFX4-IR 80 kW
0.0
Heterogeneous power table
682
hd.4
R/W
Enable heterogeneous
power control
0
ZONE 1
ZONE 2
ZONE 3
ZONE 4
0
1
X
2
X
3
X
X
4
X
5
X
X
6
X
X
7
X
X
X
8
X
9
X
X
10
X
X
11
X
X
X
12
X
X
13
X
X
X
14
X
X
X
15
X
X
X
X
Table for enabling heterogeneous power
681
I.XEU
R/W
Maximum current for heuristic power
control
0.0 ... 64.0 for GFX4 -IR 30 kW
0.0 ... 128.0 for GFX4-IR 60 kW
0.0 ... 160.0 for GFX4-IR 80 kW
0.0
Heuristic power table
680
hd.3
R/W
Enable heuristic
power control
0
ZONE 1
ZONE 2
ZONE 3
ZONE 4
0
3
X
X
5
X
X
6
X
X
7
X
X
X
9
X
X
10
X
X
11
X
X
X
12
X
X
13
X
X
X
14
X
X
X
15
X
X
X
X
NOTE: Only for GFX4-IR output OUT1 ...OUT4 with slower cycle time (1.200sec) all
HEAT or all COOL.
Table for enabling heuristic power