24
xi.l
lo.l
of.2
xs.2
l5.2
Minimum limit auxiliary
input scale
Offset correction
of aux input
0.0 ... 999.9
Maximum limit auxiliary
input scale
0.0 ... 999.9
-99.9 ... 99.9
scale points
Lower limit for setting SP
and absolute alarms
Lo.S ... Hi.S
Upper limit for setting SP
and absolute alarms
Lo.S ... Hi.S
• Out
Out
Output settings
Select
reference
signal for
alarm 1
AL.1.r, AL.2.r, AL.3.r
Select
reference
signal for
alarm 2
Select
reference
signal for
alarm 3
AL.x.r
Variable to be compared
Reference setpoint
0
PV (Process variable)
AL
1
SSP (active setpoint)
AL (only absolute)
2
PV (process variable)
AL (only relative and
referred to SP1 with
multiset function)]
Alarm
type 1
Alarm
type 2
Alarm
type 3
+8 to disable on power up until first interception
+16 to latch alarm
+ 32 Hys becomes delay time when alarm trips (0...999 sec.) (excluding symmetrical absolute)
+ 64 Hys becomes delay time when alarm trips (0...999 min.) (excluding symmetrical absolute)
AL.x.t
Direct (high limit)
Absolute or
Normal
Inverse (low limit)
relative to
Symmetrical
active setpoint
(window)
0
direct
absolute
normal
1
inverse
absolute
normal
2
direct
relative
normal
3
inverse
relative
normal
4
direct
absolute
symmetrical
5
inverse
absolute
symmetrical
6
direct
relative
symmetrical
7
inverse
relative
symmetrical
AL.1.t, AL.2.t, AL.3.t
HB alarm
function
+ 0
assigned to Out1 (only for Hb_F= 0, 1, 2)
+ 4
assigned to Out2 (only for Hb_F= 0, 1, 2)
+ 12
assigned to Out4 (only for Hb_F= 0, 1, 2)
+16
inverse HB alarm
a1.r
a2.r
a3.r
a1.t
xb.f
a2.t
a3.t
Val.
Function description
0
Relay, logic output: alarm active
on load current level lower
than setpoint during the
ON time of the control output
1
Relay, logic output: alarm active
on load current level higher
than setpoint during the
OFF time of the control output
2
Alarm active if one of functions 0 and 1
is true (OR logic between 0 and 1) (*)
3
Continuous heat alarm (**)
7
Continuous cool alarm (**)
(*) minimum setting is fixed at 12% of amperometric full scale
(**) As type 0 without reference to cycle time
Notes:
- The HB alarm is disabled if assigned to a rapid output (except codes 3 and 7)
- When the CT input is present, faceplate LED OUT3 always indicates the state of the HB alarm.