5 • “EASY” PROGRAMMING and CONFIGURATION
al.1
P.V. / S.V.
P.V. / S.V.
Process variable (PV display)
Work Setpoint (SV display) or control
output value with controller in manual
Alarm point 1 (scale points)
LEVEL 1 MENU
• CFG
• InP
h.pb
h.it
h.dt
h.p.x
Xy.i
Proportional band
for heating or hysteresis
in regulation ON/OFF
Integral time
for heating
Derivative time
for heating
Maximum power limit
for heating
0 ... 999.9%
full scale
0.00 ... 99.99 min
0.00 ... 99.99 min
0.0 ... 100.0%
Alarm 1 hysteresis
0...999 sec.
If +32 in A1.t
0...999 min.
If +64 in A1.t
±999 scale points
typ.
Probe type, signal, enable custom linearization, and main input
scale (See type table, page 6)
dp.s
lo.s
xi.s
Decimal point position for
main input scale
Minimum limit of main
input scale
Maximum limit of main
input scale
dP_S
Format
0
xxxx
1
xxx.x
2
xx.xx
3
x.xxx
min...max input range
selected in tyP
min...max input range
selected in tyP
• Out
• Prot
xi.l
lo.l
Lower limit for local
setpoint and absolute
alarms
Lo.S ... Hi.S
Upper limit for local
setpoint and absolute
alarms
Lo.S ... Hi.S
Alarm
type 1
AL.x.t
Direct (high limit)
Absolute
Normal
Inverse (low limit)
or relative
Symmetrical
to active setpoint
(window)
0
direct
absolute
normal
1
inverse
absolute
normal
2
direct
relative
normal
3
inverse
relative
normal
4
direct
absolute
symmetrical
5
inverse
absolute
symmetrical
6
direct
relative
symmetrical
7
inverse
relative
symmetrical
AL.1.t, AL.2.t, AL.3.t
a1.t
(t.2
Cycle time for
Out2
(Heat or Cool)
1...200 sec.
Pro
Protection code
Prot
Display
Modification
0
SP, alarms
SP, alarms
1
SP, alarms
SP
2
SP
+ 4
to disable InP, Out
+ 8
to disable CFG
+128 enables full configuration
THE EASY CONFIGURATION IS SUITABLE FOR VERSIONS WITH
TWO OUTPUTS (OUT1, OUT2). TO ACCESS THE OTHER
PARAMETERS, ADD 128 TO THE Pro VALUE.
+ 8 to disable at power-on until first alarm
+ 16 to enable alarm memory
+ 32 Hys becomes delay time when alarm trips (0...999 sec.)
(excluding symmetrical absolute)
+ 64 Hys becomes delay time when alarm trips (0...999 min.)
(excluding symmetrical absolute)
InP
Out
PAS = 99
Pro
Input settings
Output settings
PAS
Custom menu
Password
Protection code
CFG
S4 Jumper
(CPU)
ON