Index
MENU
[Unit] Access Default
Min/Max
Format Reg.Mode Level Ipa
Parameter Name
Description
Chapter 6 Parameter • 116
ARTDrive V2 series - Instruction Manual
B0G.02 Std enc supply
N/A
RWZ
0
0/3
DP
V-F-S-B
Easy 1927
[0] 5.41 / 8.16 V
[1] 5.68 / 8.62 V
[2] 5.91 / 9.00 V
[3] 6.16 / 9.46 V
Selection between 5V / 8V range is done through dip-switch S28.
Power supply voltage of the standard Encoder input. Increase this value in case of long
encoder cable.
It is possible to select 4 different values of internal encoder supply voltage to compensate
the voltage reduction due to encoder cable length and load current encoder.
Selection available, according to S28 jumper, are: 5.41V, 5.68V, 5.91V, 6.18V and 8.16V,
8.62V, 9.00V, 9.46V via Std enc supply parameter.
B0G.03 Std sin enc Vp
[V]
RW
0.5
0/1.5
FK
V-F-B
Full
1902
Peak voltage value of the sinusoidal encoder connected to the standard input.
B0G.04 Std dig enc mode
N/A
RWZ
0
0/ 1
DP
V-F-S-B
Full
1931
[0] FP mode
Frequency and period measuring mode
[1] F mode
Frequency measuring mode
Measuring method of the digital encoder speed connected to the standard input.
B0G.05 Exp enc type
N/A
RW
1
1/2
DK
V-F-B
Easy 1926
Encoder type connected to the expanded input port of expansion card installed:
[1]Digital
+5V Digital encoder input (select the correct jumper settings on the RV33
regulation card)
[2]Frequency inp
Digital single channel frequency input: channel A. 5V must be
connected between A and power supply common.
B0G.06 Exp enc pulses
[ppr]
RWZ
1024
Calc/Calc
FK
V-F-B
Easy 1900
Encoder pulses per revolution (ppr) value of the expanded input port of expansion card
installed.
B0G.07 Dig spd Fbk Sel
N/A
RW
0
0/1
DV
V-F-B
Easy 1940
It allows to switch the feedback between the encoder standard port “XE” (on RV33
regulation card) and the encoder expanded (from encoder optional cards: EXP-F2E and
EXP-D14A4F):
[0] Std encoder
Standard encoder input of “XE” port
[1] Exp encoder
Expanded encoder input of optional card installed
B0G.08 Speed fbk sel
N/A
RW
0
0/1
DV
V-F-B
Full
7058
Command source for the selection of the encoder used for speed feedback; factory
Содержание ARTDrive Vector V2 400Vac Series
Страница 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Страница 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Страница 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Страница 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Страница 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Страница 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...