6.5.

 

Fan Speed (U4) 

 

This setting determines the fan rotation speed, and thus the amount of air delivered. It allows to adjust 

the fan speed according to the type and quality of the fuel used. 

This setting can be set within the range of 1

÷

10, where “1” denotes minimum speed, and “10” maximum 

speed.  

You can modify this setting in a similar way to the described in sections 

6

 and 

6.2

 

6.6.

 

DHW/Return Temperature Setting (U5) 

 

This setting is available to the user 

only

 if the DHW heating option or return temperature stabilisation 

are used, and the user configured the pump with the 

F00

 service parameter by setting it to the values “01”, 

“02”, “03”, “04” (

 section 8.2 page 8). You can modify this setting in a similar way to the described in 

sections 

6

 and 

6.2

. Settings are within the range of 35°C to 65°C. 

 

6.7.

 

Anti-Legionella Function (U6) 

 

To activate the ANTI-LEGIONELLA function, set the U6 setting to 1. 

When the function is active, a blinking letter “L” is visible on the left part of the display, before the 

displayed temperature value.  

You can turn off the function by modifying the U6 setting to 0, or by pressing 

 . The anti-legionella 

function is also cancelled after a power down. 

 

The ANTI-LEGIONELLA function has higher priority over other functions, therefore it is performed 

by the Controller in the first order (superior function). 

When the function is activated, the temperature of water in the boiler is increased to 70°C and maintained 

for a period of 10 minutes. 

 

 

 

 

TURNING ON OF THE ANTY-LEGIONELLA FUNCTION CAUSES RISE OF 

THE TEMPERATURE OF HUW WATER UP TO 70

0

C. 

EXTRA CAUSION WHEN USING HUW. 

MAY RESULT IN BURNING !!! 

Содержание GH11RA

Страница 1: ...INSTRUCTION OF CONTROLLER OPERATION GH11RA FOR CONTROLLING CENTRAL HEATING BOILERS WITH FEEDING SCREW Program version 01 USER INSTRUCTIONS...

Страница 2: ...ECTION 10 5 8 MAXIMUM FEEDER TEMPERATURE DETECTION 11 6 USER SETTINGS 12 6 1 BOILER TEMPERATURE SETTING U0 12 6 2 FEEDER OPERATION DURATION U1 12 6 3 FEEDER STANDSTILL DURATION U2 12 6 4 SUSTAIN PERIO...

Страница 3: ...sed when it is necessary in described instructions to follow the sequence of carried out operations The unit may be damaged or destroyed in case of any error or proceeding in discord with the descript...

Страница 4: ...l input 4 feeder cotter pins removal sensor reed switch input RS485 for connection of the room control panel GA01HA manufactured by GECO It also contains four outputs allowing direct connection of 230...

Страница 5: ...minal causes electrical shock hazard 3 Connect the Controller to a separately installed power line protected with a properly selected quick circuit breaker or a residual current device RCD breaker Do...

Страница 6: ...n according to the factory settings Table 1 Factory settings table User parameter Description Factory setting U0 Boiler temperature setting 600 C U1 Feeder operation duration 15 s U2 Feeder standstill...

Страница 7: ...Central heating cycle HUW cycle INPUTS OUTPUTS T1 Boiler temp P1 Fuel feeder T2 Feeder temp P2 Fan T3 HUW temp P3 HUW pump C1 Reed relay P4 CH pump 5 1 2 Central heating cycle mixing pump INPUTS OUTPU...

Страница 8: ...40 C then the SH pump stop temperature is 36 C 5 1 5 Fan In the AUTO mode the fan runs continuously until the boiler temperature reaches the value set by the user in the U0 setting During that period...

Страница 9: ...to switch from automatic to manual mode and immediately stops the fan and the feeder 5 4 Viewing Temperatures After pressing the display shows water temperature at the boiler outlet Viewing temperatu...

Страница 10: ...before the power down The Controller waits 1 minute to stabilise the mains power parameters and then restores operation with the previously programmed settings During the waiting period the display s...

Страница 11: ...active only in the automatic boiler operation mode AUTO SUSTAIN When the measured temperature exceeds the value set in the F14 service setting the fuel feeder activates for the period of time set in...

Страница 12: ...Standstill Duration U2 This is the period of time between two consecutive coal feeds in the AUTO mode Settings are within the range from 5s to 250s You can modify this setting using similar procedure...

Страница 13: ...his setting in a similar way to the described in sections 6 and 6 2 Settings are within the range of 35 C to 65 C 6 7 Anti Legionella Function U6 To activate the ANTI LEGIONELLA function set the U6 se...

Страница 14: ...c Hot Water DHW pump operating with or without higher priority The DHW pump is started when the boiler outlet water temperature is higher than 40 C and higher than the water in the DHW boiler to preve...

Страница 15: ...rature to change HUW preset temperature information on all alarms to be displayed in room panel to view boiler operation state to view operation states of other units fan fuel feeder central heating p...

Страница 16: ...switch off the fan When temperature in the limiter drops by approximately 20 0 C it will be possible to restart the STB function but only manually 9 2 STB function restart manual In order to restart t...

Страница 17: ...have been noticed any irregularities in functioning of controller user should contact with the supplier producer or GECO company Professional technical assistance will be given to him If service assis...

Страница 18: ...TEP 4 Remove connectors with connected wires from plugs unscrew ground wires from PE strip loosen strip which is tightening wires and take all wires out of the controller STEP 5 Dismount a controller...

Страница 19: ...04 N Podajnik paliwa P1 56 57 Temperatura podajnika T2 05 L Pompa CO P4 A RS B Panel Pokojowy GA01HA 06 N Pompa CO P4 B RS A 07 L Pompa CWU P3 pompa miesz P8 C GND 08 N Pompa CWU P3 pompa miesz P8 D 1...

Страница 20: ...P P U H Geco Sp z o o Cholerzyn 376 32 060 Liszki tel 012 636 98 11 636 12 90 fax 012 636 20 02 http www geco pl e mail geco geco pl...

Отзывы: