6.2.3.

 

CH Pump 

Regardless of the configuration of additional pump 'F0', the CH pump: 

 is activated when the temperature of water leaving the boiler exceeds 85°C, and remains in operation 

regardless of other conditions (such as thermostat/room panel lock or DHW priority) until the outlet water 

temperature falls below 84 ° C; 

 is turned off when the boiler extinguished algorithm is implemented following a fall in temperature of 10 ° C 

, of water leaving the boiler after the fall of boiler outlet water temperature of 10 ° C – see the description of 

boiler extinguished detection for details; 

 When the anti-legionella function of the CH pump is operating, according to the algorithm contained in the 

description of anti-legionella function.

 

 

Automatic mode: 

When 

'F0'

 = 0 ÷ 2 

The CH pump is switched on when the temperature of water leaving the boiler is greater than or equal to 

the value set in parameter F6, and is disconnected when the temperature falls below F6- 3°C. When the room 

thermostat  is  locked,  the  CH  pump  disconnects  four  minutes  after  the  lock  is  activated.  When  the  room 

thermostat is locked, if the value of parameter F13 is greater than 0, the pump is connected periodically for 30 

seconds according to 

'F13'

 minute. 

When 'S0'

 = 3 

The  CH  pump  operates  as  for 

'F0'

  =  0  ÷  2,  also  when  it  is  necessary  to  heat  DHW.  (when  the  water 

temperature in the boiler is less than or equal to the set hot water temperature. 

'Tz

cwu

'

, and in the case of the 

anti-legionella  function  when  the  temperature  is  less  than  or  equal  to  75°C).  The  CH  pump  operates  as  for 

room panel/thermostat lock, connecting periodically in accordance with parameter 

'F13'

When 'S0'

 = 4 

The CH pump does not operate 

 

DHW Pump/ Mixer Pump  

In automatic and sustain mode, the DHW and mixer pump operate according to the selected configuration: 

When 'S0'

 = 0 – no pump 

The output is used for indicating an alarm (permanently switched on when the controller is in ALARM 

state). 

When 'S0'

 = 1 – Mixer pump 

The mixer pump turns off when the returning water temperature reaches the value set in parameter  'TsDHW' 

and is activated when the return water temperature falls below 'TsDHW' - 3°C. 

When ‘SO’-1 – DHW pump 

-

 

The DHW pump is connected when (1) the water temperature in the boiler is lower than the preset 

temperature in parameter 'TsDHW' and (2) the outgoing water temperature is higher than the 

temperature of the water in the  1°C, and (3) the outgoing water temperature is higher than 

40°C.

 

-

 

The DHW pump is turned off when (1) the water temperature in the boiler is above the point set in 

parameter 'TsDHW' (during operation of anti-Legionella function - when the boiler water temperature 

is higher than 75°C), or (2) the outgoing water temperature is lower than or equal to the water 

temperature in the boiler, or (3) the outgoing water temperature is below 40°C. When the anti-

legionella function is operating, the DHW pump works according to the algorithm contained in the 

description of the anti-legionella function.

 

Содержание GH10HA

Страница 1: ...circulation wood central heating boiler Program version 01 USER MANUAL We request that users carefully study applicable Instructions before connecting andstarting up any of our products Should any dou...

Страница 2: ...S 11 6 5 ALARM CONDITIONS 11 6 6 POWER FAILURE 11 6 7 BOILER BURNOUT DETECTION 12 7 USER SETTINGS 12 7 1 BOILER TEMPERATURE SETTING U0 12 7 2 FAN SPEED U1 13 7 3 HUW RETURN TEMPERATURE SETTING U2 13 7...

Страница 3: ...quence of carried out operations The unit may be damaged or destroyed in case of any error or proceeding in discord with the description Important This symbol indicates information of particular impor...

Страница 4: ...ncludes a system protecting from power outages and other different disturbances The GH10HA Controller is fitted with inputs 1 Boiler output water temperature measurement NTC sensor 2 Flue gas temperat...

Страница 5: ...00 2809 80 550 2974 90 600 3137 10 If an auxillary or relay proxy is connected a circuit breaker dedicated to this eg a varistor must be used Failure to do so may result in controller output malfuncti...

Страница 6: ...ut the plug in the power outlet 2 Turn the Controller ON by pressing Screen appears 3 Press Screen appears and the Controller starts automatic operation according to the factory settings Table 1 Facto...

Страница 7: ...Central Heating cycle HUW cycle INPUTS OUTPUTS T1 Boiler temp P1 HUW pump T2 HUW temp P2 CH pump T3 Flue gas temp P3 Fan 6 1 2 Central Heating cycle mixing pump INPUTS OUTPUTS T1 Boiler temp P1 Mixin...

Страница 8: ...g up termination after outlet water has reached preset temperature value When firing up stage exceeds time preset in service parameter F45 firing up process will be stopped and ALARM 14 will be activa...

Страница 9: ...is less than or equal to the set hot water temperature Tzcwu and in the case of the anti legionella function when the temperature is less than or equal to 75 C The CH pump operates as for room panel...

Страница 10: ...OR OPERATION ON FAN SPEED IS REDUCED IN EACH OF AUTOMATIC OPERATION MODES IF FLUE GAS TEMPERATURE EXCEEDS THE VALUE SET IN PARAMETER F42 6 3 Manual Operation Mode Pressing causes the Controller to swi...

Страница 11: ...he AL12 and AL7 alarm condition The damage of flue gas temperature sensor AL7 will not cause enter into a state of alarm the controller will work as in optimal flue gas temperature conditions AL7 alar...

Страница 12: ...d off and the Controller goes into the burnout detection mode The Controller waits for the period of time set in the F10 setting during which it checks whether a rise of 4 C occurs If YES then the bur...

Страница 13: ...Function U3 The GH10HA controller is equipment in Anti Legionella function which limit growth Legionella pneumophilia bacterium on HUW installation This function is available for users when value F00...

Страница 14: ...operation 8 2 Configuration of Additional Pump This procedure allows you to connect an additional pump that can be used as a mixing pump or a Hot Utility Water HUW pump operating with or without highe...

Страница 15: ...you to turn off the CH pump for the summer season and the boiler operates only to supply the HUW water To do this set the F00 service setting to the value of 4 9 ROOM THERMOSTAT The GH10HA controller...

Страница 16: ...ler temperature drops to a level enabling limiter reset temperature level depends on the limiter model used For safety reasons the Controller does not resume automatic operation on its own For the Con...

Страница 17: ...sensor 06 L Central Heating Pump C H 05 N Central Heating Pump C H 08 L H U W Pump Mixing Pump 07 N H U W Pump Mixing Pump 02 N Power Supply 230V 01 L Power Supply 230V Fig 1 Diagram of connection ou...

Страница 18: ...ctive collection of worn out electrical and electronic equipment It means that this product should not be disposed of with other household wastes Proper disposal of aged and worn out electrical and el...

Страница 19: ......

Страница 20: ...P P U H Geco Sp z o o Cholerzyn 376 32 060 Liszki Poland ph 012 636 98 11 636 12 90 fax 012 636 20 02 http www geco pl e mail geco geco pl...

Отзывы: