DIS. 0534026   COD. 27102280 

Istruzione / User’s Manual / Manuel d’utilisation

 

Pag.4/8

 

 

 

 

GECA Srl Via E. Fermi 98, 25064 Gussago (Brescia) Italy http://www.gecasrl.it Tel:+39 030/3730218  Fax: +39 030/3730228

 

 

 

Nota

: La verifica della taratura va effettuata solo da personale addestrato e autorizzato. Nel caso i valori non siano quelli 

richiesti contattare il nostro laboratorio. 
La verifica della Taratura può essere fatta utilizzando il nostro kit TC011 (Vedi istruzioni fornite con il Kit), collegare la 
bombola al portagomma del Flussometro, far affluire il gas (a circa 0,3 l/min), attendere circa 3 minuti e verificare che la 
centralina sia in allarme come decritto nel capitolo “FUNZIONAMENTO”

 

GB 

 DESCRIPTION 

The 

CTR137

 is a central unit for wall installation, IP65, with a catalytic sensor for flammable gas. It is normally powered 

at 230 AC and/or 12÷24Vdc/ac. 
Two different models are available and the only difference is the calibration carried out with specific gas:  

 the CTR137M should be used with Methane plants. 

 the CTR137G should be used with LPG plants.  

On the front plate the LED bar shows both the working condition and the gas concentration detected by the sensor. The 
instrument is supplied with two alarm levels with sealed-type outputs relays and with tension-free change over contacts. 
Furthermore it has an auxiliary outputs relays in positive security for FAULT situation and an auxiliary input (AUX) con-
nectable to our Manual NC Resetting valve with Positioning Sensor. 
Fig. 1 shows a typical mains supply wiring diagram with alarm siren and normally closed solenoid valve. 

OPERATIONAL DESCRIPTION 

PREHEATING

: when the central unit is supplied, the “yellow” LED starts to flash and it means the sensor is heating. Af-

ter 60 seconds, the “Green” Led switches on and it means the normal working.   

NORMAL OPERATING

: the central unit reads the gas concentration through the internal sensor 

1st Red LED:

 

it switch on if the gas concentration is higher than 5% LIE. 

2nd Red LED:

 

it switch on if the gas concentration is higher than 10% LEL; if within 4 seconds the gas is not reduced, 

the “PREAL.”relay will activate. This relay is normally used as a prealarm for the controlling of a siren (

SE301A). 

3rd Red LED:

 

it switch on if the gas concentration is higher than 20% LIE; if the gas persists, the 4th Red LED “STOP” 

switches on within 30 seconds and the “ALARM” relay will activate. It is normally used to stop the gas through the man-
ual reset solenoid valve (NO or NC) and/or the interruption of the electrical energy. 

If it has been installed a manual reset solenoid valve N.C. with magnetic sensor connected to “AUX” input, in the case that the 
gas is still open, the yellow LED and the “FAULT “ Relay will activate (

see “FAULTS” section

). 

RESET KEY

:

 The alarm condition remains latched, LEDs and relays remain activated, even if the gas concentration is 

reduced, because the mounted valve is closed. To reset the normal working conditions and/or switch off the siren push 
the "RESET" button. 

Buzzer 

the  “PREAL.”  relay  will  be  deactivated  and  the  Red  Led  flashes,  only  if  the  gas  concentration  is  higher  than 

10% of LIE. After 20 seconds, both of them will return in preallarm. (the siren rings) 

If it has been used a manual reset solenoid valve NC with the magnetic sensor  and in the case that it is snapped, the 
Yellow led will switch off and the “FAULT” relay will be deactivated. (See FAULTS section). 

Alarm

 

Reset

 

The central unit will begin to the normal working, only if the gas concentration is lower than 10% LIE, the 

“ALARM” relay will be deactivated and the 3

rd

 and 4th Red LED will switch off. If activated, the “FAULT” relay will be de-

activated and the “Yellow” LED will switch off. (see FAULTS sections). 

Warning

:

 Pushing the RESET button, if the gas concentration is higher than F.S., it can happen that the first “PREAL.” 

relay will be deactivated and the first three Red LEDs will switch off. The Yellow LED will illuminate and the “FAULT” re-
lay will activate. A fault on the sensor is most probable in this case. Eliminate the alarm’s cause, if the condition persist 
pushing the RESET button, please consult the FAULTS section. 

FAULTS

:  The central unit signal  different kind  of  failures  activating the Yellow LED and the FAULT  relay. That is nor-

mally activated. The "FAULT" relay, if necessary, can be used both to signal remotely an occurred damage and to signal 
the absence of power to the instrument. 

Yellow  and  Green  LEDs  and  FAULT  relay  activate:

 

this  happens  when  the  catalytic  sensor  is  not  working.  If  this 

condition do not change, it will be necessary to replace the unit or to send it to the supplier back to repair.

 

Yellow, Green, 4th Red LEDs and FAULT and ALARM relays activate:

 

(only after press RESET key) this happens 

when the catalytic sensor is not working or in few cases when there is a higher gas concentration. In this case the central 
unit will remain in alarm, as described in the 

OPERATING>WARNING Section

. If there are not any gas leaks and the condition 

is not change, it will be necessary to replace the unit and/or send it back to the supplier to repair. 

Manual  reset  solenoid  valve  NC  with  magnetic  sensor  failure: 

this  situation  appears  ONLY  when  is  installed  an 

electro valve with magnetic sensor; if it not close the gas, the ALARM relay will activate (gas concentration higher than 
20% LIE) and the magnetic sensor signals to the central unit the this bad working. In this case all led will be lighted and 
relays will be activated. The failure condition (yellow led lighted and FAULT relay activated) will be cancelled if pressing 
the RESET key, the solution of the problem will be visualized. 

INSTALLATION 

The 

CTR137

 should be installed according to the national disposition in force on the matter.  

Model 

CTR137

M positioning:

 Methane

 (CH

4

) is a combustible gas lighter than air. Its density related to air is 0.55; its 

LEL (Lower Explosion Limit) is 5% v/v (Volume). 

The instrument should be fixed at 30 cm from the ceiling

 and be placed 

at 1-1.5 meter from the gas appliance, far from the room corners or from ventilation intakes. 

Содержание CTR137M

Страница 1: ...ntervention de alarme 10 LIE LEL Intervento blocco 2nd Alarm intervention Seuil d intervention de blocage 20 LIE LEL Contatti rel Contacts rating Contact relais 230Vac 3A SPDT Tempo di risposta T90 Re...

Страница 2: ...one e nel caso in cui essa sia scattata si spegner il Led giallo e si disattiver il rel FAULT vedi sezione Guasti pi avanti Ripristino dopo un Allarme la centralina torner al funzionamento normale sol...

Страница 3: ...e causano una temporanea perdita di sensibilit Questi inibitori sono gli Alogeni l Idrogeno solforato il Cloro gli Idrocarburi clorurati Trielina o Tetracloruro di carbonio Dopo un breve tempo in aria...

Страница 4: ...nditions and or switch off the siren push the RESET button Buzzer the PREAL relay will be deactivated and the Red Led flashes only if the gas concentration is higher than 10 of LIE After 20 seconds bo...

Страница 5: ...vity These inhibitors include Hydrogen sulphide Chlorine Chlorinated hydrocarbons and halogenated compounds The sensitivity is recovered after a short period of running in clear air FUNTIONAL TESTING...

Страница 6: ...ngement R armement apr s une d alarme La centrale revient au fonctionnement normal si la concentration de gaz est inf rieure 10 de la LIE Le relais ALARME sera d sactiv le 3 et 4 led rouge s tendent S...

Страница 7: ...ique il est conseill d effectuer une v rification de fonctionnement tous les 6 12 mois ATTENTION cette proc dure doit tre ex cut e avec une extr me attention par un personnel autoris et comp tent car...

Страница 8: ...norm ferm e 230Vca NC C NA NC C NA NC C NA L N SE301A PREAL ALARM Valvola NC FAULT AUX Fig 4 Collegamento con valvola a riarmo manuale Norm Aperta Wiring diagram with a normally open manual resetting...

Отзывы: