SETPOINT EXAMPLES FOR HEAT PUMP ADJUSTMENTS IN
DIFFERENT HEATING NETWORKS
Set points of the heating circuits:
*HC = Heating circuit
Domestic hot water set points:
Heat pump’s set points:
Row number
Control row
Factory setting
Under floor
heating
Radiator heat-
ing
Air heating
HC1* HC2*
HC3*
700
1000
1300
Opearating mode
Automatic
710
1010
1310
Comfort set point
20
712
1012
1312
Reduced set point
19
714
1014
1314
Frost protection set point
15
720
1020
1320
Heating curve slope
0,5
0,5
(0,3-0,5)
0,8
(0,5-1,2)
0,8
(0,5-1,2)
740
1040
1340
Flow temp setpoint min
12
12
12
12
741
1041
1341
Flow temp setpoint max
45
45
(35-45)
55
(45-60)
55
(45-60)
750
1050
1350
Room sensor compensation
20 %
730
1030
1330
Summer/winter heating limit
16
Row number
Control row
Factory setting
1600
Operating mode
On
1610
Nominal set point
50°C
Row number
Control row
Factory
setting
Underfloor
heating
Radiator heat-
ing
Air heating
2840
Return water temperature switching differen-
tial
6
6
8
(8-10)
10
Содержание GEMINI 40
Страница 1: ...Installation Operation and Maintenance Manual GEMINI Heat Pump WWW GEBWELL FI...
Страница 57: ...v1 6 29082018 57 20 ENERGY LABELS...
Страница 58: ......
Страница 59: ......
Страница 60: ......
Страница 61: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......