![Gebwell GEMINI 40 Скачать руководство пользователя страница 48](http://html1.mh-extra.com/html/gebwell/gemini-40/gemini-40_installation-operation-and-maintenance-manual_573180048.webp)
48
Gebwell GEMINI
No: Failure message
Sensor Description
Cause
Measure
Measure
225: Under pressure
E9
Under pressure switch
has tripped.
Too low a flow in collec-
tor. The shut-off/balanc-
ing valves in the collec-
tion loop are shut off. A
clogged strainer. Too lit-
tle liquid on the collection
loop. The water in the
heating system is too cold
(under 15°C)
Clean the strainer on
the collector. Add
more liquid in the col-
lector if needed. If
necessary, contact a
qualified technician.
Check the functioning of the collec-
tor. Check the functioning of the
source pump.
226: Compressor 1 over
load
E11
Compressor motor pro-
tection has tripped.
The
compressor
has
tripped the motor protec-
tion.
Set compressor motor
protection (F1) on
ON-position. If nec-
essary, contact a qual-
ified electrician.
Check the power supply of the heat
pump. Check the functioning of the
compressor.
243: Swimming pool
sensor
B13
Failure in the electrical
system
324: BX, same sensors
The sensors with same
marking are connected to
BX entries.
Failure in the electrical
system
Contact a qualified
technician.
Change the correct sensor ad-
dresses.
324: BX/extramod. same
sensors
The sensors with same
marking are connected to
BX entries.
Failure in the electrical
system
Contact a qualified
technician.
Change the correct sensor ad-
dresses.
357: Cool.circuit 1 output
water temp.
The temperature of the
output water of cooling
circuit is too low.
The control valve is in
manual mode. Incorrectly
set value.
Check the minimum
temperature level of
the cooling circuit.
358: Soft starter
E25
Soft starter has given an
alarm.
Heat pump motor protec-
tion is turned off. The heat
pump's power supply
phases are reversed. In-
stantaneous power failure.
Power supply is missing a
phase. The fuse is blown.
Check that the motor
protection
is
on.
Change the phase se-
quence on the plug.
Check that the heat
pump’s fuses are in-
tact. Contact a quali-
fied technician.
Содержание GEMINI 40
Страница 1: ...Installation Operation and Maintenance Manual GEMINI Heat Pump WWW GEBWELL FI...
Страница 57: ...v1 6 29082018 57 20 ENERGY LABELS...
Страница 58: ......
Страница 59: ......
Страница 60: ......
Страница 61: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......