Calibration
The Sola shower valve has a factory set outlet temperature of 38˚C via the security setting.
This is based on a balanced supply pressure and a stable hot water inlet temperature of 65˚C.
However, the calibration point MUST be checked and re-set as necessary to suit site
conditions.
Care must be taken when re-calibrating the shower valve as I
NCORRECT CALIBRATION
CAN CAUSE INJURY
.
• Remove the indice (5), retaining screw (6), handle (7) and the temperature stop ring (11).
• Temporarily refit the handle (7) and move to the position for the hottest water and allow the
outlet temperature to stabilise.
• Using a digital thermometer it is possible to increase or reduce the mixed water outlet
temperature until 38˚C is re-established, by slowly rotating the handle.
• Remove the handle (7) and refit the temperature stop ring (17) onto the splined section of
the cartridge at the maximum temperature position.
• Refit the handle in the reverse order.
PLEASE NOTE THAT ONCE CALIBRATED, THE SECURITY SETTING WILL ONLY BE
38˚C UNDER THE SUPPLY CONDITIONS USED FOR CALIBRATION.
Cartridge Replacement
5
6
7
17
18
Isolate both the hot and cold water supplies
Remove the indice (5), and unscrew retaining screw (6).
Remove the handle (7) and the temperature stop ring (17).
Using a suitable spanner unscrew the cartridge (18).
Replace with a new cartridge and assemble in the reverse
Spares
A full range of spares are available for this product.
PLEASE NOTE:
Only genuine spares should be used.