22
D
GB
F
E
96192-11.2015-DGbFE
HG22e / ...
125-4(S) A
160-4(S) A
190-4(S) A
Designation
Ref. No.
Ref. No.
Ref. No.
Set gaskets
80590
Valve plate set
80305
80306
80306
Piston/connecting
rod set
80302
80303
80304
Connecting rod set
08422
Accessories available can be found on the Internet at www.gea.com
7.4 Accessories
Only use original GEA spare parts!
7.3 Spare parts recommendation
7.1 Preparation
7.2 Work to be carried out
7
|
Maintenance
Oil change:
In principle, an oil change is not mandatory if the system is correctly manufactured
and operated.
However, based on decades of experience we recommend that the following oil change/service
work is carried out:
-
First oil change during the first maintenance system.
-
Then after every 10,000 – 12,000 operating hours, though no more than
3 years, cleaning oil and suction filter at the same time.
Annual checks:
Oil level, tightness, running noise, pressures, temperatures, function of auxiliary
devices such as a oil sump heater, pressure switch.
WARNING! Before starting any work on the compressor:
Switch off the compressor and secure it to prevent a restart.
Relieve compressor of system pressure.
Prevent air from infiltrating the system!
After maintenance has been performed:
Connect safety switch.
Evacuate compressor.
Release switch lock.