3.7
Grasso V 300 .. 1800 (T), WITHOUT GMM
The schedule below has to be used when GMM is not applied.
Hint!
In case Grasso Maintenance Monitor (GMM) is applied, the
maintenance intervals will be based on actual measured values. If
GMM is applied, refer to Section 3.6, Page 42
Service and maintenance schedules Grasso V 300 .. 1800 (T), excl. GMM
Item
Description
Actions
Checkpoint
Running hours * 1000
10
0.1
Yearly
3
6
-
-
-
9
-
12
-
-
15
-
18
-
21
-
-
24
-
-
27
30
-
-
-
33
-
-
-
36
1
Oil
CL
RE
CL
RE
RE
RE
RE
RE
Oil suction filter
2
RE
11
RE
RE
RE
RE
RE
RE
RE
Oil discharge
filter
3
-
ME
ME
ME
ME
ME
ME
ME
Oil analysis
4
RE
RE
-
RE
RE
RE
RE
RE
Oil refreshment
(If hygroscopical
oil is used
replace this
always after each
opening of
compressor or
installation)
5
Oil pump
-
IC/CL
-
IC/CL IC/CL IC/CL IC/CL IC/CL
Housing and
element
6
-
IC/CL
-
IC/CL IC/CL IC/CL IC/CL IC/CL
Control and
lubrication oil
pressure
regulator
7a
Crankshaft
-
-
-
-
-
-
IC/M
E
IC/M
E
Main and
intermediate
bearing bushes
10
Check after every maintenance job the settings and working of all safety devices, regulators and the
running conditions according to the Service Instruction Manual (SIM)
11
A running-in oil discharge filter is factory mounted. This running-in filter has to be replaced after max. 100
running hours by a permanent filter. One permanent filter is supplied together with the compressor.
MAINTENANCE
Grasso V 300 .. 1800 (T), WITHOUT GMM
0089288gbr_11
46
30.10.2017
Содержание Grasso V Series
Страница 6: ...0089288gbr_11 6 30 10 2017 ...
Страница 8: ...0089288gbr_11 8 30 10 2017 ...
Страница 10: ...0089288gbr_11 10 30 10 2017 ...
Страница 61: ...Fig 16 Grasso V 6 Pre lubrication valve APPENDIX Product Information PI 0089288gbr_11 30 10 2017 61 ...