Electrical connection
5.3 Terminal cross section for leads
Compressor type
Minimum terminal cross section
Direct start
Part winding start
EX-HG(X)44e/475-4 (HC)
3 x 10 mm²
6 x 6 mm²
EX-HG(X)44e/475-4 S (HC)
3 x 16 mm²
6 x 10 mm²
EX-HG(X)44e/565-4 (HC)
3 x 16 mm²
6 x 10 mm²
EX-HG(X)44e/565-4 S (HC)
3 x 16 mm²
6 x 16 mm²
EX-HG(X)44e/665-4 (HC)
3 x 16 mm²
6 x 16 mm²
EX-HG(X)44e/665-4 S (HC)
3 x 16 mm²
6 x 16 mm²
EX-HG(X)44e/770-4 (HC)
3 x 16 mm²
6 x 16 mm²
EX-HG(X)44e/770-4 S (HC)
3 x 16 mm²
6 x 16 mm²
EX-HG(X)56e/850-4 (HC)
3 x 25 mm²
6 x 16 mm²
EX-HG(X)56e/850-4 S (HC)
3 x 25 mm²
6 x 25 mm²
EX-HG(X)56e/995-4 (HC)
3 x 25 mm²
6 x 16 mm²
EX-HG(X)56e/995-4 S (HC)
3 x 25 mm²
6 x 25 mm²
EX-HG(X)56e/1155-4 (HC)
3 x 25 mm²
6 x 16 mm²
EX-HG(X)56e/1155-4 S (HC)
3 x 25 mm²
6 x 25 mm²
To limit the heating of conducting parts, the minimum terminal cross sections, indicated in the table
have to be followed.
- At ambient temperatures > 40 °C, supply lines and cable/line bushings with a temperature
resistance of at least 90 °C must be used.
- The interpretation of the minimum terminal cross sections refer to the voltage range of 400 V,
50 Hz at 30 °C ambient temperature.
5.2 Information for contactor and motor contactor selection
All protection devices and switching or monitoring units must be fitted in accordance with the local
safety regulations and established specifications (e.g. VDE) as well as with the manufacturer’s infor
-
mation.
Motor protection switches are required!
Motor contactors, feed lines, fuses and motor
protection switches must be rated on the basis of the maximum working current (see name plate).
For motor protection use a current-dependent and time-delayed overload protection device for moni
-
toring all three phases. Set the overload protection device so that it must be actuated within 2 hours,
if there is 1.2 times the max. working current.
WARNING
Always install all electrical peripheral devices in an external
control cabinet outside the explosion-endangered area!