GE WiMAX WX-I210+c Скачать руководство пользователя страница 6

WiMAX

 

SmartMeter by GE 

3.2  Liquid Crystal Display Information 

 

The liquid crystal display  (LCD) is shown. The numbered list coincides with the numbers in 
Figure 3-2. 

 

 

 

 

 

 

 

 

Figure 3-2: Liquid Crystal Display Information 

1.  The “TEST” annunciator indicates the meter is in Test mode. 
 
2.  The “ALT” annunciator indicates the meter is in Alternate Display mode. 
 
3.  The three small digits are used to display the current display label or code. “CA” or 

“Er” appearing in this location indicates a Caution or Error message in the display. 

 
4.  These letters are used to display the units of measure for the quantity currently 

being displayed. For example, energy displays will have a “kW h” annunciator and 
Apparent Power will have a “kVA” annunciator.  

 
5.  The letters A through D indicate the time-of-use (TOU) rate that is in effect. Only 

one letter at a time is displayed when the meter is operating in TOU Mode. If no 
letters are lit, the meter is in a non-TOU rate. 

 
6.  This display indicates an end-of-interval (EOI) condition. 
 
7.  W hen displayed, the “A” annunciator indicates the A voltage is present at the 

meter. If this annunciator is blinking, phase-A voltage is low. 

 

The “B” annunciator will only be displayed during an all-segments display. 
 
W hen displayed, the “C” annunciator indicates the C voltage is present at the 
meter. If this annunciator is blinking, C voltage is low. (Network meters only) 

 

8.  The left-right arrows indicate watt hour direction of energy flow. The right arrow will 

be lit if the energy is delivered; the left arrow will be lit if the energy is received. 
The up-down arrows indicate VArh direction of quadergy flow. The up arrow will be 
lit if the quadergy is lagging; the down arrow will be lit if the quadergy is leading.  
 
The meter’s magnitude indicator consists of three segments, used to simulate the 
rotation of the disk on an electromechanical meter. Each state change represents 

Содержание WiMAX WX-I210+c

Страница 1: ...WiMAX SmartMeter by GE Basic Manual WX I210 c WiMAX SmartMeter by GE ...

Страница 2: ...tion 1 2 Installation Instructions 2 3 Labels and Display Information 3 3 1 Nameplate Information and Labels 3 3 2 Liquid Crystal Display Information 4 3 2 1 Display Examples 5 4 Service and Repair 7 4 1 Service 7 4 2 Repair 7 4 3 Returning a Meter 7 ...

Страница 3: ...ure 1 1 WX I210 c WiMAX SmartMeter by GE The WX I210 c incorporates a wide range of additional advanced metering features including an extended range of software configurable metrology capabilities soft switches accurate timekeeping via a harmonic clock with an oscillating crystal and battery backup power source to accurately maintain time during power outage conditions enhanced energy demand and ...

Страница 4: ...the following installation steps are performed 1 Take the last meter read on the existing meter 2 Remove existing meter s tamper indication seal 3 Remove existing meter from socket 4 Replace new meter into socket 5 Install new tamper indication seal 6 Re energize the circuits to the meter ...

Страница 5: ...3 1 for a graphic representation of the meter nameplate The meter nameplate is found on the front of the meter Figure 3 1 Meter Nameplate The nameplate provides the following information Meter type Utility information and bar code area Meter serial number Operating frequency Test ampere value Watt hour and test constants Current and voltage rating Wiring configuration ANSI form factor Available so...

Страница 6: ...played when the meter is operating in TOU Mode If no letters are lit the meter is in a non TOU rate 6 This display indicates an end of interval EOI condition 7 When displayed the A annunciator indicates the A voltage is present at the meter If this annunciator is blinking phase A voltage is low The B annunciator will only be displayed during an all segments display When displayed the C annunciator...

Страница 7: ...e states change in decreasing order Note If the calculated phasor VAh is below the programmed creep threshold the meter will turn off the Wh and VArh direction arrows 9 These characters display the programmed metering quantities There are three possible decimal point positions located between the four rightmost digits 3 2 1 Display Examples The following figures show examples of WiMAX SmartMeter d...

Страница 8: ...e Figure 3 4 Alternate Display Figure 3 4 shows the following conditions 1 Meter is in Alternate Display mode 2 Display label 108 is displayed 3 Phase A and C voltages are present 4 Six digit display of quadergy kVArh 5 Displayed quantity is measured in kVArh 6 Meter is displaying previous season data 7 The two blocks indicate State 1 of the magnitude indicator 8 Quadergy kVArh is leading 9 Energy...

Страница 9: ... design the repair of on board components is not recommended Instead return the whole meter to General Electric as described in the following paragraph 4 3 Returning a Meter If you wish to return a meter call your General Electric sales representative for a Returned Material Authorization RMA The entire meter should be returned with the GE supplied Returned Material Authorization information form ...

Отзывы: