background image

12

31-5000710   Rev. 2

Installation Instructions

Install Condensate Drain (cont.)

1.  Pour several quarts of water into the drain pan, 

enough to fill drain trap and line. 

2.  Check to make sure the drain pan is draining 

completely, no leaks are found in drain line fittings, 
and water is draining from the end o the primary 
drain pan. 

3.  Correct any leaks found.

Insulate pipe as needed 

Vent must extend a minimum of 2” 
above the drain pan 

Drain Pan 

Pitch horizontal 

drain lines 

downward 1” per 10' 

2” Min. 

3/4” MPT Connector 

2” Min. 

Drain Line and Vent Tee 

Ve

n

“T

” 

Drain Line 

Clean Out 
Press in 
(DO NOT GLUE) 

Reducing Tee with 
1” Slip Hex Plug 

Install Condensate Drain

The air handler is provided with 3/4” NPT condensate 
drain connections. 

A field fabricated secondary drain pan with a drain 
pipe to the outside of the building is required in all 
installations over a finished living space or in any area 
that may be damaged by overflow from the main drain 
pan. In some localities, local codes require secondary 
drain pan for any horizontal installation. The secondary 
drain pan must have a larger footprint than the air 
handler. 

1.  Remove the appropriate panel knockouts for drains. 

See “Drain Pan Connections” section. You may need 
to remove the indoor coil assembly from the cabinet. 

2.  Determine the drain connection to be used and 

note differences between the primary (green) and 
secondary (red) openings. Drain plugs are provided 
for all openings; remove and discard the appropriate 
plugs with 1/2” drive ratchet and verify that remaining 
plugs are tight (2.5 ft-lbs). Attach drain line to pan 
with 3/4” male pipe thread PVC fittings. Hand tight is 
adequate—do not over tighten and do not reduce the 
line size.

3.  Secondary drain connections should be connected 

to a separate drainage system. Run this drain to 
a place in compliance with local installation codes 
where is will be secondary drain indicates a plugged 
primary drain.

4.  Install a 2” trap in the primary drain line as close to 

the unit as practical. Make sure the top of the trap 
is below the connection to the drain pan to allow 
complete drainage of the pan. 

NOTE: 

Horizonal runs must also have an anti-siphon 

air vent (standpipe) installed ahead of the horizontal 
run. An extremely long horizontal run may require an 
oversized drain line to eliminate air trapping. 

NOTE: 

Do not operate air handler without a drain trap. 

The condensate drain is on the negative pressure 
side of the blower; therefore air can be drawn into the 
condensate line and will prevent positive drainage 
without a proper trap. 

5.  Route the drain line to the outside or to an 

appropriate drain. Drain lines must be installed so 
they do not block serviceaccess to the front of the air 
handler. A 24” clearance is required for filter, coil, or 
blower removal and service access. 

NOTE: 

Check local codes before connecting the drain 

line to an existing drainage system. 

6.  Insulate the drain lines where sweating could cause 

water damage. 

Upon completeion of installation, it is the responsibility 
of the installer to ensure the drain pan(s) is capturing 
all condensate, and all condensate is draining properly 
and not getting into the duct/system. 

Содержание UUY24ZGDA

Страница 1: ...tructions READ CAREFULLY KEEP THESE INSTRUCTIONS The manufacturer recommends installing AHRI listed matched indoor and outdoor system Installing approved matched indoor and outdoor system will provide...

Страница 2: ......

Страница 3: ...________ Date of purchase To register your new air handler go to GEAppliances com register and input the model serial number information on this page To receive a 10 year compressor and parts warranty...

Страница 4: ...age along its length or at either end WARNING This unit is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge T...

Страница 5: ...is much higher than R22 Use ACR copper tubing with adequate wall thickness Use a tubing bender to change piping direction Make sure the radius of the bend is no less than 4 If the pipe is bent repeat...

Страница 6: ...trict inspection and operational testing at the factory 5 For technical assistance please contact GE Appliances technical support 6 If the product is malfunctioning and or is inoperable please contact...

Страница 7: ...l R 410A flaring tool Hex wrench Hole saw 2 1 4 Insulation Refrigerant scale Level Manifold gauge set Measuring tape Micron gauge Mini split adapter 5 16 F to 1 4 M Nitrogen Pipe cutter PVC pipe Razor...

Страница 8: ...service access The air handler can be installed in a closet with a false bottom to form a return air plenum or be installed with a return air plenum under the air handler Model Dimension inch mm Width...

Страница 9: ...Installation Instructions Model Filter Size inch UUY24ZGDA 20 x 20 UUY36ZGDA UUY48ZGDA 21 x 20 UUY60ZGDA Model Motor 230V 60Hz HP FLA UUY24ZGDA 1 2 2 1 UUY36ZGDA UUY48ZGDA 1 3 2 UUY60ZGDA Model Cooli...

Страница 10: ...e air handler s duct system causing death or serious illness 1 Checking Product Received After receiving the product please check for any damage caused by transportation Shipping damage is the respons...

Страница 11: ...the lines in a direct path avoiding unnecessary turns and bends 2 Ensure that the suction line is insulated over the entire exposed length and that both suction and liquid lines are not in direct cont...

Страница 12: ...th 1 2 drive ratchet and verify that remaining plugs are tight 2 5 ft lbs Attach drain line to pan with 3 4 male pipe thread PVC fittings Hand tight is adequate do not over tighten and do not reduce t...

Страница 13: ...be led through GL HUHQW UXEEHU ULQJV RI WKH HOHFWULF ER FRYHU 2 Maintain as much separation as possible between the power and control wiring 3 High and low voltage wires should be secured separately...

Страница 14: ...nstalling heat make sure the L1 L2 wires are connected to the heater breaker then wire the ground wire Use proper wire size as specified in this manual for heater assemblies If there is no heat kit to...

Страница 15: ...e suction line connection after brazing is completed If necessary the bulb can be installed on a vertical suction line In this instance the bulb must be placed before any trap with the bulb s capillar...

Страница 16: ...motor is with earthing wire 6 As for wiring please refer to the parameters before of MCA and MOP of heat kit on the nameplate for CB1 please refer to parameters after of MCA and MOP for CB2 YEGN G CN...

Страница 17: ...flow settings for the air handler is Level 4 Air flow can be adjusted by using the control board dip switches different speeds according to the system static pressure Fan speed settings are listed bel...

Страница 18: ...evel 4 Default ON ON OFF OFF ON ON ON ON Level 5 ON OFF ON ON ON ON ON ON Level 6 ON OFF ON OFF ON ON ON ON Level 7 ON OFF OFF ON ON ON ON ON Level 8 ON OFF OFF OFF ON ON ON ON UUY48ZGDAB Level 1 OFF...

Страница 19: ...60 1480 1400 1310 1210 1080 930 Level 6 1640 1590 1500 1420 1330 1220 1100 960 Level 7 1690 1620 1520 1440 1350 1250 1150 Level 8 1660 1600 1540 1440 1320 1220 UUY48ZGDAB Level 1 1640 1500 1450 1400 L...

Страница 20: ...consecutive sound when unit is running or after running That s sound for operation of drainage system The unit blows out dust When unit runs after no operation for a long period Dust in indoor unit i...

Страница 21: ...turn on signal the running indicator light is on when detecting the indoor fan turning off signal the running indicator light is off When detecting a system failure the running indicator light flashe...

Страница 22: ...22 31 5000710 Rev 2 Notes...

Страница 23: ...been maintained annually by a licensed HVAC technician proof required Damage caused by a used or unapproved component or part by GE Appliances a Haier company e g a used and or unapproved condenser a...

Страница 24: ...dy provided in this warranty is exclusive and is granted in lieu of all other remedies This warranty does not cover incidental or consequential damages Some states and provinces do not allow the exclu...

Страница 25: ...tion LISEZ ET CONSERVEZ CES INSTRUCTIONS Le fabricant recommande d installer un syst me int rieur et ext rieur assorti r pertori AHRI L installation d un syst me int rieur et ext rieur appari approuv...

Страница 26: ..._______________________ Num ro de s rie _______________________________________ Date d achat Ce manuel contient les instructions d installation pour les unit s int rieures en hauteur Pour la s rie Fle...

Страница 27: ...essure Utilisez cet quipement uniquement aux fins auxquelles il est fait mention dans ce manuel d utilisation Avant son utilisation ce climatiseur doit tre install correctement en conformit avec les i...

Страница 28: ...u le tube capillaire Un dimensionnement incorrect de la tuyauterie va diminuer le rendement Les pointes de pression du r frig rant R410A sont beaucoup plus lev es que celles du R22 Utilisez une tuyaut...

Страница 29: ...de l aide sur le plan technique veuillez contacter l assistance technique de GE Appliances 6 Si le produit ne fonctionne pas bien ou s il n est pas utilisable veuillez contacter l assistance techniqu...

Страница 30: ...po Isolant Balance pour r frig rant Niveau Ensemble de manom tre de pression Ruban mesurer Microvacuom tre Adaptateur mini split 5 16 po F 1 4 po M Azote Coupe tuyau Tuyau PVC Couteau utilitaire Al s...

Страница 31: ...it de traitement d air peut tre install e dans un placard dot d un double fond pour former un pl num de reprise d air ou install e avec un pl num de reprise d air sous l unit Instructions d installati...

Страница 32: ...ructions d installation Mod le Capacit de refroidissement tonne l ment chauffant en option kW UUY24ZGDA 2 0 5 8 10 UUY36ZGDA 3 0 5 8 10 UUY48ZGDA 4 0 10 15 20 UUY60ZGDA 5 0 10 15 20 Mod le Taille du f...

Страница 33: ...itement d air ferait circuler les missions de monoxyde de carbone dans l espace occup occasionnant le d c s ou une maladie s v re 1 V rification du produit re u Une fois le produit re u veuillez v rif...

Страница 34: ...s et les courbes inutiles 2 Assurez vous que le tuyau d aspiration est isol sur toute sa longueur expos e et qu il n est pas ainsi que le tuyau de liquide en contact direct avec des planchers des murs...

Страница 35: ...o et v rifiez que les bouchons restants sont tanches 2 5 pi lb Fixez la conduite de vidange au bac avec des raccords en PVC filetage m le de 3 4 Le serrage manuel est ad quat ne serrez pas trop et ne...

Страница 36: ...distance que possible entre les c blages d alimentation et de commande 3 Les c bles de haute et basse tension doivent tre fix s s par ment Fixez ceux de haute tension l aide de grandes brides et ceux...

Страница 37: ...e chauffage est install pour la premi re fois assurez vous que les c bles L1 et L2 sont raccord s au disjoncteur de chauffage puis au fil de mise la terre Utilisez le bon calibre de fil comme mentionn...

Страница 38: ...iration apr s avoir termin le brasage Si n cessaire on peut installer l ampoule sur un tuyau d aspiration vertical Dans ce cas l ampoule doit tre plac e avant tout siphon avec le tube capillaire de l...

Страница 39: ...motor is with earthing wire 6 As for wiring please refer to the parameters before of MCA and MOP of heat kit on the nameplate for CB1 please refer to parameters after of MCA and MOP for CB2 YEGN G CN...

Страница 40: ...Le d bit d air peut tre r gl en utilisant les commutateurs DIP du tableau de commande de diff rentes vitesses selon la pression statique du syst me Les param tres de vitesses de ventilateur sont indi...

Страница 41: ...ON ON ON ON Niveau 4 D faut ON ON OFF OFF ON ON ON ON Niveau 5 ON OFF ON ON ON ON ON ON Niveau 6 ON OFF ON OFF ON ON ON ON Niveau 7 ON OFF OFF ON ON ON ON ON Niveau 8 ON OFF OFF OFF ON ON ON ON UUY48...

Страница 42: ...390 1310 1160 1080 1000 Niveau 5 1560 1480 1400 1310 1210 1080 930 Niveau 6 1640 1590 1500 1420 1330 1220 1100 960 Niveau 7 1690 1620 1520 1440 1350 1250 1150 Niveau 8 1660 1600 1540 1440 1320 1220 UU...

Страница 43: ...n C est le syst me d vacuation du condensat qui fonctionne L unit souffle de la poussi re Lorsque l unit fonctionne apr s une longue p riode d inutilisation La poussi re dans l unit int rieure est sou...

Страница 44: ...oin de fonctionnement est allum lorsque le signal d arr t du ventilateur int rieur le t moin d alimentation est allum Le t moin d alimentation clignote lors de la d tection d un mauvais fonctionnement...

Страница 45: ...t ou de conditions similaires Un Produit qui n a pas t install ou r par par un technicien agr en chauffage ventilation et climatisation La main d uvre et les services connexes pour la r paration ou l...

Страница 46: ...le reste de la garantie de base standard Le recours autoris dans cette garantie est exclusif et il est accord en remplacement de tout autre recours Cette garantie ne couvre pas les dommages accessoir...

Страница 47: ...GUARDE ESTAS INSTRUCCIONES El fabricante recomienda instalar un sistema de interior y exterior combinado homologado por AHRI La instalaci n de un sistema homologado para interiores y exteriores propo...

Страница 48: ...de modelo _____________________________________ __ N mero de serie _____________________________________ __ Fecha de compra Este manual contiene instrucciones de instalaci n para unidades internas en...

Страница 49: ...CENDIO Puede ocasionar lesiones o la muerte No guarde ni use materiales combustibles gasolina u otros vapores inflamables y l quidos cerca de ste o de otros electrodom sticos Las regulaciones federale...

Страница 50: ...ntaminantes El uso de una tuber a de tama o inadecuado reducir el rendimiento La presi n m xima de R410A es muy superior a R22 Use una tuber a de cobre con el grosor de pared adecuado A fin de evitar...

Страница 51: ...vo en f brica 5 Para solicitar asistencia t cnica por favor comun quese con el soporte t cnico de GE Appliances 6 Si el producto funciona mal y o no funciona por favor comun quese con el soporte t cni...

Страница 52: ...islante Balanza para refrigerante Nivel Set del calibrador del colector Cinta de medici n Medidor de micrones Adaptador para mini split 5 16 F a 1 4 M Nitr geno Cortatubos Tuber a de PVC Cuchillo filo...

Страница 53: ...zador se podr instalar en un armario con fondo falso para formar un pl num de retorno de aire o se podr instalar con un pl num de retorno de aire debajo del climatizador Instrucciones de Instalaci n M...

Страница 54: ...ucciones de Instalaci n Modelo Capacidad de enfriamiento ton Calentador el ctrico opcional kW UUY24ZGDA 2 0 5 8 10 UUY36ZGDA 3 0 5 8 10 UUY48ZGDA 4 0 10 15 20 UUY60ZGDA 5 0 10 15 20 Modelo Tama o del...

Страница 55: ...ductos del climatizador ocasionando la muerte o enfermedades graves 1 Control del Producto Recibido Luego de recibir el producto por favor controle que no posea da os ocasionados por su traslado Cualq...

Страница 56: ...as por un camino directo evitando giros y curvas innecesarios 2 Aseg rese de que la tuber a de succi n est aislada en toda su longitud expuesta y que tanto las tuber as de succi n como de l quido no...

Страница 57: ...est n ajustados 2 5 pies libras Conecte la l nea de drenaje a la bandeja con accesorios de PVC con rosca macho de 3 4 El ajuste manual es adecuado no ajuste en exceso y no reduzca el tama o de la tube...

Страница 58: ...pa de la caja el ctrica 2 Mantenga tanta separaci n como sea posible entre la corriente y el cableado del control 3 Los cables con niveles de voltaje altos y bajos se deber n asegurar de forma separad...

Страница 59: ...ue los cables L1 L2 est n conectados al disyuntor y luego conecte el cable a tierra Use el tama o de cable adecuado de acuerdo con lo especificado en este manual para ensambles de calefactores Si no h...

Страница 60: ...ucci n una vez finalizada la soldadura De ser necesario la l mpara se podr instalar en una tuber a de succi n vertical En esta instancia la l mpara se deber colocar delante de cualquier precinto con l...

Страница 61: ...motor is with earthing wire 6 As for wiring please refer to the parameters before of MCA and MOP of heat kit on the nameplate for CB1 please refer to parameters after of MCA and MOP for CB2 YEGN G CN...

Страница 62: ...flujo de aire se podr ajustar usando diferentes velocidades en los interruptores DIP del tablero de control de acuerdo con la presi n est tica del sistema Las configuraciones de velocidad del ventilad...

Страница 63: ...ON ON ON ON Nivel 4 D faut ON ON OFF OFF ON ON ON ON Nivel 5 ON OFF ON ON ON ON ON ON Nivel 6 ON OFF ON OFF ON ON ON ON Nivel 7 ON OFF OFF ON ON ON ON ON Nivel 8 ON OFF OFF OFF ON ON ON ON UUY48ZGDAB...

Страница 64: ...ut 1390 1310 1160 1080 1000 Nivel 5 1560 1480 1400 1310 1210 1080 930 Nivel 6 1640 1590 1500 1420 1330 1220 1100 960 Nivel 7 1690 1620 1520 1440 1350 1250 1150 Nivel 8 1660 1600 1540 1440 1320 1220 UU...

Страница 65: ...de su funcionamiento Se trata del sonido de funcionamiento del sistema de drenaje La unidad sopla polvo Cuando la unidad se pone en funcionamiento luego de un per odo prolongado de inactividad El pol...

Страница 66: ...se encender al detectar la se al de apagado del ventilador interior la luz indicadora de funcionamiento se apagar Al detectar una falla en el sistema la luz indicadora de funcionamiento parpadear Dif...

Страница 67: ...ctrica incorrecta Da o resultante de inundaciones incendios viento iluminaci n accidentes o condiciones similares Un producto que no fue instalado o su servicio t cnico no fue realizado por un t cnico...

Страница 68: ...garantizada en lugar de todas las dem s soluciones Esta garant a no cubre da os incidentales o consecuentes Algunos estados y provincias no permiten la exclusi n de da os incidentales o consecuentes...

Отзывы: