GE Multilin
L60 Line Phase Comparison System
5-245
5 SETTINGS
5.6 CONTROL ELEMENTS
5
•
AR 3-P DEAD TIME 1
: This is the dead time following the first three pole trip. This intentional delay can be used for a
high-speed three-pole autoreclose. However, it should be set longer than the estimated de-ionizing time following the
three-pole trip.
•
AR 3-P DEAD TIME 2
: This is the dead time following the second three-pole trip or initiated by the
AR 3P TD INIT
input.
This intentional delay is typically used for a time delayed three-pole autoreclose (as opposed to high speed three-pole
autoreclose).
•
AR 3-P DEAD TIME 3(4)
: These settings represent the dead time following the third (fourth) three-pole trip.
•
AR EXTEND DEAD T 1
: This setting selects an operand that will adapt the duration of the dead time for the first shot
to the possibility of non-simultaneous tripping at the two line ends. Typically this is the operand set when the communi-
cation channel is out of service
•
AR DEAD TIME 1 EXTENSION
: This timer is used to set the length of the dead time 1 extension for possible non-
simultaneous tripping of the two ends of the line.
•
AR RESET
: This setting selects the operand that forces the autoreclose scheme from any state to reset. Typically this
is a manual reset from lockout, local or remote.
•
AR RESET TIME
: A reset timer output resets the recloser following a successful reclosure sequence. The setting is
based on the breaker time which is the minimum time required between successive reclose sequences.
•
AR BKR CLOSED:
This setting selects an operand that indicates that the breakers are closed at the end of the reset
time and the scheme can reset.
•
AR BLOCK
: This setting selects the operand that blocks the autoreclose scheme (it can be a sum of conditions such
as: time delayed tripping, breaker failure, bus differential protection, etc.). If the block signal is present before autore-
close scheme initiation the
AR DISABLED
FlexLogic™ operand will be set. If the block signal occurs when the scheme
is in the RIP state the scheme will be sent to lockout.
•
AR PAUSE
: The pause input offers the ability to freeze the autoreclose cycle until the pause signal disappears. This
may be done when a trip occurs and simultaneously or previously, some conditions are detected such as out-of step or
loss of guard frequency, or a remote transfer trip signal is received. When the
pause signal
disappears the autoreclose
cycle is resumed. This feature can also be used when a transformer is tapped from the protected line and a reclose is
not desirable until the it is disconnected from the line. In this situation, the reclose scheme is
paused
until the trans-
former is disconnected.
•
AR INCOMPLETE SEQ TIME
: This timer is used to set the maximum time interval allowed for a single reclose shot. It
is started whenever a reclosure is initiated and is active until the
CLOSE BKR1
or
CLOSE BKR2
signal is sent. If all con-
ditions allowing a breaker closure are not satisfied when this time expires, the scheme goes to “Lockout”. The mini-
mum permissible setting is established by the
AR 3-P DEAD TIME 2
timer setting. Settings beyond this will determine the
wait time
for the breaker to open so that the reclose cycle can continue and/or for the
AR PAUSE
signal to reset and
allow the reclose cycle to continue and/or for the
AR BKR1 BLK
signal to disappear and allow the
AR CLOSE BKR1
signal
to be sent.
•
AR BLOCK BKR2
: This input selects an operand that will block the reclose command for breaker 2. This condition can
be for example: breaker low air pressure, reclose in progress on another line (for the central breaker in a breaker and
a half arrangement), or a sum of conditions combined in FlexLogic™.
•
AR CLOSE TIME BKR2
: This setting represents the closing time for the breaker 2 from the moment the ‘Close’ com-
mand is sent to the moment the contacts are closed.
•
AR TRANSFER 1 TO 2
: This setting establishes how the scheme performs when the breaker closing sequence is 1-2
and breaker 1 is blocked. When set to “Yes” the closing command will be transferred direct to breaker 2 without waiting
the transfer time. When set to “No” the closing command will be blocked by the
AR BKR1 BLK
signal and the scheme
will be sent to lockout by the incomplete sequence timer.
•
AR TRANSFER 2 TO 1
: This setting establishes how the scheme performs when the breaker closing sequence is 2-1
and breaker 2 is blocked. When set to “Yes” the closing command will be transferred direct to breaker 1 without waiting
the transfer time. When set to “No”, the closing command will be blocked by the
AR BKR2 BLK
signal and the scheme
will be sent to lockout by the incomplete sequence timer.
•
AR BKR1 FAIL OPTION
: This setting establishes how the scheme performs when the breaker closing sequence is 1-
2 and Breaker 1 has failed to close. When set to “Continue” the closing command will be transferred to breaker 2 which
will continue the reclosing cycle until successful (the scheme will reset) or unsuccessful (the scheme will go to Lock-
out). When set to “Lockout” the scheme will go to lockout without attempting to reclose breaker 2.
Содержание UR series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 132: ...4 30 L60 Line Phase Comparison System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Страница 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...