5-158
L60 Line Phase Comparison System
GE Multilin
5.5 GROUPED ELEMENTS
5 SETTINGS
5
IAC CURVES:
The curves for the General Electric type IAC relay family are derived from the formulae:
,
(EQ 5.12)
where:
T
= operate time (in seconds),
TDM
= Multiplier setting,
I
= Input current,
I
pkp
= Pickup Current setting,
A to
E
=
constants,
t
r
= characteristic constant, and
T
RESET
= reset time in seconds (assuming energy capacity is 100%
and
RESET
is “Timed”)
Table 5–19: GE TYPE IAC INVERSE TIME CURVE CONSTANTS
IAC CURVE SHAPE
A
B
C
D
E
T
R
IAC Extreme Inverse
0.0040
0.6379
0.6200
1.7872
0.2461
6.008
IAC Very Inverse
0.0900
0.7955
0.1000
–1.2885
7.9586
4.678
IAC Inverse
0.2078
0.8630
0.8000
–0.4180
0.1947
0.990
IAC Short Inverse
0.0428
0.0609
0.6200
–0.0010
0.0221
0.222
Table 5–20: IAC CURVE TRIP TIMES
MULTIPLIER
(TDM)
CURRENT ( I / I
pickup
)
1.5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
IAC EXTREMELY INVERSE
0.5
1.699
0.749
0.303
0.178
0.123
0.093
0.074
0.062
0.053
0.046
1.0
3.398
1.498
0.606
0.356
0.246
0.186
0.149
0.124
0.106
0.093
2.0
6.796
2.997
1.212
0.711
0.491
0.372
0.298
0.248
0.212
0.185
4.0
13.591
5.993
2.423
1.422
0.983
0.744
0.595
0.495
0.424
0.370
6.0
20.387
8.990
3.635
2.133
1.474
1.115
0.893
0.743
0.636
0.556
8.0
27.183
11.987
4.846
2.844
1.966
1.487
1.191
0.991
0.848
0.741
10.0
33.979
14.983
6.058
3.555
2.457
1.859
1.488
1.239
1.060
0.926
IAC VERY INVERSE
0.5
1.451
0.656
0.269
0.172
0.133
0.113
0.101
0.093
0.087
0.083
1.0
2.901
1.312
0.537
0.343
0.266
0.227
0.202
0.186
0.174
0.165
2.0
5.802
2.624
1.075
0.687
0.533
0.453
0.405
0.372
0.349
0.331
4.0
11.605
5.248
2.150
1.374
1.065
0.906
0.810
0.745
0.698
0.662
6.0
17.407
7.872
3.225
2.061
1.598
1.359
1.215
1.117
1.046
0.992
8.0
23.209
10.497
4.299
2.747
2.131
1.813
1.620
1.490
1.395
1.323
10.0
29.012
13.121
5.374
3.434
2.663
2.266
2.025
1.862
1.744
1.654
IAC INVERSE
0.5
0.578
0.375
0.266
0.221
0.196
0.180
0.168
0.160
0.154
0.148
1.0
1.155
0.749
0.532
0.443
0.392
0.360
0.337
0.320
0.307
0.297
2.0
2.310
1.499
1.064
0.885
0.784
0.719
0.674
0.640
0.614
0.594
4.0
4.621
2.997
2.128
1.770
1.569
1.439
1.348
1.280
1.229
1.188
6.0
6.931
4.496
3.192
2.656
2.353
2.158
2.022
1.921
1.843
1.781
8.0
9.242
5.995
4.256
3.541
3.138
2.878
2.695
2.561
2.457
2.375
10.0
11.552
7.494
5.320
4.426
3.922
3.597
3.369
3.201
3.072
2.969
IAC SHORT INVERSE
0.5
0.072
0.047
0.035
0.031
0.028
0.027
0.026
0.026
0.025
0.025
1.0
0.143
0.095
0.070
0.061
0.057
0.054
0.052
0.051
0.050
0.049
2.0
0.286
0.190
0.140
0.123
0.114
0.108
0.105
0.102
0.100
0.099
4.0
0.573
0.379
0.279
0.245
0.228
0.217
0.210
0.204
0.200
0.197
6.0
0.859
0.569
0.419
0.368
0.341
0.325
0.314
0.307
0.301
0.296
8.0
1.145
0.759
0.559
0.490
0.455
0.434
0.419
0.409
0.401
0.394
10.0
1.431
0.948
0.699
0.613
0.569
0.542
0.524
0.511
0.501
0.493
T
TDM
A
B
I I
pkp
⁄
(
)
C
–
------------------------------
D
I I
pkp
⁄
(
)
C
–
(
)
2
--------------------------------------
E
I I
pkp
⁄
(
)
C
–
(
)
3
--------------------------------------
+
+
+
⎝
⎠
⎜
⎟
⎛
⎞
×
=
T
RESET
TDM
t
r
1
I I
pkp
⁄
(
)
2
–
--------------------------------
×
=
Содержание UR series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 132: ...4 30 L60 Line Phase Comparison System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Страница 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...