2020003701   (08/06)

 

                                                                                                    Page 3 of 4 

I

NSTALLATION 

(

CONT

.):

 

3. 

The TVSS can be installed in any orientation, however  

special consideration should be given to allow periodic 
visual inspection of the status indicator lamps. 

C

ONNECTION

 

1. 

TR5451 and TR5452 Model TVSS units come equipped 

with 10 AWG connection wires to allow termination to the 
electrical system.   It is important that the TVSS be installed 
in a location that is as close to the termination point as 
possible.   Connection wires should be trimmed to prevent 
excessive lead length.  Do not coil, loop or make sharp 
bends with the connection wires.   Every inch of wire that 
can be trimmed away will aid the TVSS in it’s ability to 
provide the best possible protection level for your system.

 

2. 

Refer to the wiring diagrams on the left for your selected 

model type.   The TR5451 and TR5452 models must be 
connected to a branch circuit breaker.  The breaker must 
not exceed a 30A / 22kAIC rating.

 

3. 

Remote Alarm Relay Contacts are provided as an 

optional feature on some model types.  Contacts are 
standard 1 Form C type, rated 5 A, 250 VAC max.  Refer to 
the wiring diagram on the left for contact configuration. The 
relay contact will be closed between “NO” and “COM” under 
normal operation.   If the TVSS fails, or if power is lost to 
the TVSS,  the relay contact will open between “NO” and 
“COM” and close between “NC” and “COM”.  

 

4. 

Model types with 210N and 210S part number suffixes 

are fitted with jumpers on the alarm terminal block which 
connects the “COM” and “NC” contacts to the ground 
terminal of the TVSS.  This feature should only be utilized 
for OEM installations where this type of configuration has 
been evaluated as suitable.  For all other installations, the 
jumpers should be removed so that the alarm contacts will 
function normally per paragraph 3 above.

 

O

PERATION

 

1. 

When energized, the green LED status indicator lamps 

located on the front of the TVSS will be illuminated.  For 
TR5451 models, there is 1 indicator.  For TR5452 models, 
there are 2.

 

2. 

If one or both of the of the status indicators are not 

illuminated, verify the integrity of the connection 
terminations, breaker status, the electrical supply voltage 
and the electrical system grounding.

 

3. 

If no problems are found, the TVSS could be in failure 

mode and require replacement.  Contact your local GE 
representative for further assistance.

 

   

M

AINTENANCE

 

1. 

TR5451 and TR5452 model types contain no user 

serviceable parts and require no annual maintenance or 
calibration.   Only a periodic visual inspection of the LED 
indicators is required.  Do not attempt to repair or otherwise 
alter the TVSS unit.  

 

 
 
 

903-640-0555
800-950-2281

NOTE:  If lamp is out, replace unit

LISTED (48E6)

UL 1449, 2

ND

EDITION

FOR INDOOR USE ONLY

 

DUAL PHASE TVSS

120 VAC 50/60HZ

SUPPRESSION VOLTAGES

330 L-N
600 L-L

TVSS
PART# ACT452120210N
DATE CODE:     WO#

Green

Black

White

NO  COM  NC

Optional Alarm 

Terminal

30 A.  / 22kAIC
Max.

903-640-0555
800-950-2281

NOTE:  If lamp is out, replace unit

LISTED (48E6)

UL 1449, 2

ND

EDITION

FOR INDOOR USE ONLY

 

DUAL PHASE TVSS

120 VAC 50/60HZ

SUPPRESSION VOLTAGES

330 L-N
600 L-L

TVSS
PART# ACT452120210N
DATE CODE:     WO#

Green

Black

Black

White

30 A.  / 22kAIC
Max.

NO  COM  NC

Optional Alarm 

Terminal

TR451 Wiring Diagram 

TR452 Wiring Diagram 

Содержание TR5451

Страница 1: ...to ensure that the proper TVSS model number has been selected for your SPECIAL ATTENTION MUST BE GIVEN TO VERIFY THAT A PROPER NEUTRAL GROUND XO BOND HAS BEEN MADE WHEN POWER IS SUPPLIED FROM AN UPSTREAM TRANSFORMER OR ANY OTHER TYPE OF SEPARATELY DERIVED POWER SOURCE FAILURE TO PROVIDE THIS BOND AS REQUIRED PER ARTICLE 250 30 OF THE NATIONAL ELECTRICAL CODE CAN RESULT IN ELEVATED PHASE TO GROUND ...

Страница 2: ...OLTAGE NOMINAL VOLTAGE 50 60hZ MODEL TYPE L1 L2 N VOLTAGE RATINGS POWER SOURCE CONFIGURATIONS L1 N INSTALLATION POWER MUST BE PROVEN DISCONNECTED BEFORE STARTING INSTALLATION INSPECTION OR MAINTENANCE FAILURE TO DO SO MAY CAUSE SERIOUS INJURY DEATH AND OR PROPERTY DAMAGE Before attempting installation make sure that the pre installation requirements of this manual have been satisfied If the status...

Страница 3: ...ground terminal of the TVSS This feature should only be utilized for OEM installations where this type of configuration has been evaluated as suitable For all other installations the jumpers should be removed so that the alarm contacts will function normally per paragraph 3 above OPERATION 1 When energized the green LED status indicator lamps located on the front of the TVSS will be illuminated Fo...

Страница 4: ...ieved the published design specifications A certificate of compliance is available upon request NOTICE These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise which are not covered suffic...

Отзывы: