GE Multilin
T60 Transformer Protection System
5-197
5 SETTINGS
5.6 GROUPED ELEMENTS
5
Figure 5–83: GROUND DISTANCE ZONE 1 OP SCHEME
Figure 5–84: GROUND DISTANCE ZONE 2 OP SCHEME
For ground distance zone 2, there is a provision to start the zone timer with the other distance zones or loop pickup
flags to avoid prolonging ground distance zone 2 operation if the fault evolves from one type to another or migrates
from zone 3 or 4 to zone 2. The desired zones should be assigned in the trip output element to accomplish this
functionality.
837018A7.CDR
AND
AND
AND
OR
OR
OR
OR
** D60, L60, and L90 only. Other UR-series models apply regular current seal-in for zone 1.
AND
FLEXLOGIC OPERAND
GND DIST Z1 PKP A
GND DIST Z1 SUPN IN
OPEN POLE OP **
FLEXLOGIC OPERANDS
SETTING
GND DIST Z1 DELAY
T
PKP
0
T
PKP
0
T
PKP
0
FLEXLOGIC OPERAND
GND DIST Z1 PKP B
FLEXLOGIC OPERAND
GND DIST Z1 PKP C
GND DIST Z1 OP A
GND DIST Z1 OP B
FLEXLOGIC OPERANDS
GND DIST Z1 OP C
FLEXLOGIC OPERAND
GND DIST Z1 OP
OR
AND
OR
837037A1.CDR
from the open pole detector element D60, L60, and L90 only)
FLEXLOGIC OPERAND
OPEN POLE OP **
FLEXLOGIC OPERAND
GND DIST Z2 PKP A
FLEXLOGIC OPERAND
GND DIST Z2 PKP B
FLEXLOGIC OPERAND
GND DIST Z2 PKP C
TIMER
0 ms
20 ms
TIMER
0 ms
20 ms
TIMER
0 ms
20 ms
SETTING
GND DIST Z2 DELAY
TPKP
0
SETTING
GND DIST Z2 DELAY
TPKP
0
SETTING
GND DIST Z2 DELAY
TPKP
0
FLEXLOGIC OPERAND
GND DIST Z2 OP A
FLEXLOGIC OPERAND
GND DIST Z2 OP B
FLEXLOGIC OPERAND
GND DIST Z2 OP C
FLEXLOGIC OPERAND
GND DIST Z2 OP
FLEXLOGIC OPERAND
TRIP Z2 GR TMR INIT
OR
OR
OR
AND
OR
AND
OR
AND
AND
AND
from the trip output element
NOTE
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...