Table 13
System Connectivity
HART Physical Device Type
Valve positioner; HART device type 7, Device type 202, 0, 00CA)
DD Registered with HART
Communication Foundation
Yes
Integration with HART Host software
ValVue AMS SNAP-ON application available, Plug-In Application For
Yokogawa PRM, ValVue For Honeywell FDM, Device Type Manager
(DTM) for FDT Host
Diagnostics
Standard:
Alarms, cycle counter, travel accumulator, time open, time close, time
near close, Step Test, Positioner Test
Advanced:
Includes Standard Diagnostics and the following: Low Air Supply
alarm, Valve Signature (Friction, spring range, seat profile)
Table 14
Pneumatics Single Acting Standard Flow
Air Supply
Dry, oil-free, 5 micron filtered air (per ISA S7.3)
Action
Direct Acting
Supply Pressure
20-100 psi max. (1.4 to 6.9 bar)
Regulate 5 to 10 psi above actuator spring range. Do not
exceed actuator rating.
Air Delivery - Single Acting Relay
10.0 scfm (283 l/m) at 30 psi (2.1 bar) supply
16.6 scfm (470 l/m) at 60 psi (4.2 bar) supply
23.3 scfm (660 l/m) at 90 psi (6.3 bar) supply
Air Capacity
(flow coefficient)
Loading CV = 0.57
Venting CV = 0.53
Air Consumption
0.2 scfm (5.7 sl/m) at 30 psi (2.1 bar) supply
0.26 scfm (7.4 sl/m) at 45 psi (3.1 bar) supply
Air Supply Failure
Single Acting Relay
On supply failure the actuator output fails to atmosphere.
Some overshoot may occur when air pressure returns
after a period without air supply pressure. Always set
control set point to 0%, and put the process control
system in manual, for smooth recovery from air supply
failure.
Loss of Input Signal
Actuator Output fails to atmosphere
Output Pressure
0-150 psi (10.3 bar) max
68
GE Oil & Gas
ValVue SVI II AP Quick Start
Содержание SVI II AP-2
Страница 6: ...GE Oil Gas SVI II AP Quick Start Guide 6 ...
Страница 10: ...10 GE Oil Gas ValVue SVI II AP Quick Start This page intentionally left blank ...
Страница 64: ...64 GE Oil Gas ValVue SVI II AP Quick Start This page intentionally left blank ...
Страница 90: ...90 GE Oil Gas ValVue SVI II AP Quick Start Spare Parts ...
Страница 91: ...91 Specifications and Spare Parts ...
Страница 92: ...92 GE Oil Gas ValVue SVI II AP Quick Start ...