55
Check Out,
Calibration
Calibration
CAUTION
Pilot Trim Valve Applications require the use of the Manual
Stop calibration procedure (refer to Configuration and
Calibration of the SVI II AP Instruction Manual, EW2002-AP).
Do not run Find Stops or the ValVue Setup Wizard on valves
with Pilot Trim or damage to the valve will occur.
To calibrate the SVI II AP:
1. Observe the display following power-up. The SVI II AP powers up in the
previously active mode either MANUAL or NORMAL (operating) mode:
In NORMAL mode, the display alternates between POS and SIGNAL.
In MANUAL, the display alternates between POS –M and SIG.
2. With
MANUAL
mode displayed, press
*
to select the MANUAL mode.
3. Press
+
again;
CONFIG
appears. Pressing
+
again brings
CALIB
.
4. Select
CALIB
by pressing
*
. STOPS appears. The valve moves full open and
back to full closed. Observe all warnings.
5. Press
*
to cause the valve to stroke and to automatically calibrate valve travel.
6. After the
STOPS
procedure finishes, press
+
twice until
TUNE
appears.
Содержание SVI II AP-2
Страница 6: ...GE Oil Gas SVI II AP Quick Start Guide 6 ...
Страница 10: ...10 GE Oil Gas ValVue SVI II AP Quick Start This page intentionally left blank ...
Страница 64: ...64 GE Oil Gas ValVue SVI II AP Quick Start This page intentionally left blank ...
Страница 90: ...90 GE Oil Gas ValVue SVI II AP Quick Start Spare Parts ...
Страница 91: ...91 Specifications and Spare Parts ...
Страница 92: ...92 GE Oil Gas ValVue SVI II AP Quick Start ...