5 SETPOINTS
5.2 SETPOINTS MENU
5
5.2.10 SYNCHRONOUS SLIP
FUNCTION:
The value stored here is the slip at which the SPM will close the field contactor (FAR). It is expressed as per-
cent slip.
MOTOR TYPE:
Collector-Ring
EXAMPLE:
To close the field contactor (apply the field) when the motor reaches 94.5% of synchronous speed, the
SYNC
SLIP
setpoint is determined as follows:
100% speed – 94.5% speed = 5.5% sync slip
5.2.11 STALL TIME
FUNCTION:
This setpoint determines the allowable time that power may be applied to the motor during locked rotor condi-
tions. This information may normally be found on the motor control data sheet available from the motor manu-
facturer.
MOTOR TYPE:
Collector-Ring and Brushless
5.2.12 RUN TIME
FUNCTION:
Run time is the time that the motor may run at 50% speed and is expressed as a multiple of the allowable
motor stall time.
MOTOR TYPE:
Collector-Ring
EXAMPLE:
If the motor stall time is 10 seconds and
RUN TIME
is set to 3.00, then then the motor can run at:
3.00
×
10 sec. = 30 seconds at 50% speed
SYNC SLIP: 5.0%
ENTER to modify
Range: 0.5 to 10%
Step: 0.1%
STALL TIME: 10 s
ENTER to modify
Range: 1 to 40 seconds
Step: 1
RUN TIME: 1.05 x ST
ENTER to modify
Range: 1.05, 1.46, 2.05, 3.00 x
STALL TIME
Содержание SPM Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi SPM Synchronous Motor Protection Control GE Power Management TABLE OF CONTENTS...
Страница 74: ...6 4 SPM Synchronous Motor Protection Control GE Power Management 6 2 STATUS 6 ACTUAL VALUES 6...
Страница 96: ...8 6 SPM Synchronous Motor Protection Control GE Power Management 8 3 DC CURRENT TRANSFORMER 8 ACCESSORIES 8...
Страница 120: ...C 2 SPM Synchronous Motor Protection Control GE Power Management C 1 WARRANTY APPENDIXC C...
Страница 124: ...iv SPM Synchronous Motor Protection Control GE Power Management INDEX...
Страница 125: ...GE Power Management SPM Synchronous Motor Protection Control NOTES...