10-
4
SPM Synchronous Motor Protection & Control
GE Power Management
10.4 COLLECTOR-RING MOTOR POWER FACTOR TRIP TEST
10 FUNCTIONAL TESTS
10
10.4 COLLECTOR-RING MOTOR POWER FACTOR TRIP TEST
10.4.1 SETUP
1.
Connect as for Collector-Ring Power Factor Test in the previous section.
2.
Connect timer to TRIP relay.
10.4.2 RELAY PROGRAMMING
a) CONFIGURATIONS
Program as defaults shown in Section 5.4: CONFIGURATIONS MENU on page 5–12 except for following
exceptions
•
MOTOR: Collector-Ring
b) SETPOINTS
Program as defaults shown in 5.2: SETPOINTS MENU on page 5–2.
10.4.3 TEST
1.
Apply control power to relay and wait for self test diagnostic to complete. Should get SPM READY mes-
sage and TRIP relay should close.
2.
Turn on current source and function generator.
3.
Open MX switch
4.
FAR contact should close followed by FCX contact. FIELD IS APPLIED message should momentarily flash
on screen.
5.
PF metered value will now be displayed along with other metered values.
6.
Vary voltage angle as in table below and check PF reading.
Table 10–3: COLLECTOR-RING MOTOR PF TRIP TEST RESULTS
SETPOINTS
INPUT/EXPECTED
RESULTS
PF TRIP
PF DELAY
ANGLE
EXPECTED PF
TRIP TIME
–0.60
1
302°
–0.52
–0.70
5
309°
–0.63
–0.80
3
317°
–0.74
1.00
10
341°
–0.95
Содержание SPM Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi SPM Synchronous Motor Protection Control GE Power Management TABLE OF CONTENTS...
Страница 74: ...6 4 SPM Synchronous Motor Protection Control GE Power Management 6 2 STATUS 6 ACTUAL VALUES 6...
Страница 96: ...8 6 SPM Synchronous Motor Protection Control GE Power Management 8 3 DC CURRENT TRANSFORMER 8 ACCESSORIES 8...
Страница 120: ...C 2 SPM Synchronous Motor Protection Control GE Power Management C 1 WARRANTY APPENDIXC C...
Страница 124: ...iv SPM Synchronous Motor Protection Control GE Power Management INDEX...
Страница 125: ...GE Power Management SPM Synchronous Motor Protection Control NOTES...