OPM_SGS_ISG_M75_M75_2US_V010.doc
Installation Guide
SG Series 750 UL S2
&
SG Series 750 T12 UL S2
In case of parallel system, try to place the UPS modules in sequence of their numbers (marked on
the packing).
If the units are positioned “
side by side
”, the side panels must be mounted on all units.
SGS_750
_RPA dis
position_
GE_01_U
S
UPS 2
3 - 4 - 5 - 6
UPS
UPS 1
Fig. 3.4.1-5 SG Series 750 & SG Series 750 T12 RPA system disposition
3.4.2 Battery location
Batteries require a well-ventilated room with controlled temperature to obtain reliable operation.
The
Battery
can be installed immediately adjacent to the UPS (left or right side) or remotely from the
UPS.
If the
Battery
is installed remotely from the UPS, a wall mounted DC disconnect device must be installed
within line-of-site to both the UPS and the
Battery
.
The optimal room temperature for
Battery
storage is
68°F
(20°C)
to
77°F
(25°C) and shall never exceed
the range
-4°F
(-20°C) to
104°F
(40°C).
The life of valve-regulated batteries will be reduced by 50% for each additional
18°F
(10°C) that the
Battery
ambient temperature is above
77°F
(25°C).
The
Battery System
associated with larger UPS is usually either rack mounted or installed in multiple
Battery Cabinets
.
Installation and assembly must be made according to the local standards and
Battery System
manufacturer‘s recommendations.
The
Battery Circuit Breaker
or
Battery Fuse Box
must be mounted as near as possible to the
Battery
.
WARNING !
Battery
installation and connection must be performed by QUALIFIED PERSONNEL
only.
Read all safety instructions before proceeding with the installation.