ZONELINE SERIES – DIRECT ELECTRICAL CONNECTION

4. CONNECT THE CORDSET

Plug the connectors, provided in the Direct Connect Kit, 
fully into place in the corresponding mating connectors. 
Be sure the locking tabs at the sides are engaged.

Installation Instructions

Power supply kit - 

Appearance may vary

15A

20A and 30A

NOTE:

 RAK315D and RAK515D will only have 

one power connector.

1. REMOVE ROOM FRONT

Remove the room cabinet by pulling it out at the bottom to 
release it (1); then lift it up to clear the rail along the unit 
top (2)

For a direct connect kit installation with a flex cable, 
proceed to step 5A.

For a direct connect kit installation with a sub-base and 
chaseway, skip ahead to step 5B.

2.  REMOVE JUNCTION BOX COVER

Remove the junction box cover by removing the screw 
holding it to the assembly.

3.  INSTALL JUNCTION BOX 

(230/208V units)

Install the junction box by engaging the left tabs of 
the junction box with the slots on the control housing, 
align the screw hole at the top and drive the screw until 
secure.

It is the responsibility of the installer to ensure the connection of components is done in accordance with the NEC, 

local codes, ordinances and regulations.

Direct connection to branch circuit wiring inside the junction box must be made by connecting as follows.

Recommended branch circuit wire sizes*

Nameplate maximum circuit breaker size

AWG wire size**

15A
20A
30A

14
12
10

AWG—American Wire Gauge
* Single circuit breaker from main box
** Based on copper wire, single-insulated conductor at 60°C

For GE Zoneline AZ45 & AZ65 Series Units

This kit must be used in conjunction with a GE 
RAK4002D junction box kit. Order this kit separately.

Junction box

Junction box 
cover

Knock out

Screw

Tabs on 
Junction 
Box

Slots on 
Control 
Housing

Содержание RAK315D

Страница 1: ...Z9V series GE Zoneline units GE Zoneline AZ45 and AZ65 series units must be installed with a junction box RAK4002D purchased separately RAK515D RAK520D and RAK530D kits These kits are for use with 265V AZ45 AZ65 AZ95 and AZ9V series GE Zoneline Units FOR 230 208 VOLT DIRECT CONNECT APPLICATIONS ONLY IMPORTANT Some local electrical codes and customer requirements require PTAC units to be direct con...

Страница 2: ...ew holding it to the assembly 3 INSTALL JUNCTION BOX 230 208V units Install the junction box by engaging the left tabs of the junction box with the slots on the control housing align the screw hole at the top and drive the screw until secure It is the responsibility of the installer to ensure the connection of components is done in accordance with the NEC local codes ordinances and regulations Dir...

Страница 3: ...C and UL listed electrical connectors and techniques 2 For 20A and 30A power supply kits plug in the personality jumper for heater selection 3 Carefully tuck all wires and connections back inside the junction box Be sure there are no loose connections or stray uninsulated wires exposed 4 Place the junction box cover in place Replace the two screws removed earlier and tighten securely 5 Replace the...

Страница 4: ...in receptacle in the junction box 6 Replace the junction box cover by replacing the three screws removed earlier NOTICE Wire junction box to match figure above Building supply wires and supply cord wires must both be secured with zip tie and oriented vertically Installation Instructions 1 REMOVE JUNCTION BOX COVER Remove the junction box cover by removing the three screws holding it to the assembl...

Страница 5: ...NS À CONNEXION DIRECTES DE 265 VOLTS UNIQUEMENT IMPORTANT La connexion d un produit de 265 VCA à un circuit de dérivation DOIT être réalisée conformément avec le Code national de l électricité Le branchement de cet appareil à une prise exposée montée sur le bâtiment n est pas permis par le code Ces modèles doivent être installés en utilisant l ensemble de bloc d alimentation approprié pour l inten...

Страница 6: ...ans le haut et vissez la vis 9RWUH LQVWDOODWHXU D OD UHVSRQVDELOLWp GH V DVVXUHU TXH OHV FRQQH LRQV GHV FRPSRVDQWV VRQW HႇHFWXpHV HQ FRQIRUPLWp DYHF OH FRGH national de l électricité et les codes et règlements locaux La connexion directe à un câblage de circuit de dérivation à l intérieur de la boîte de jonction doit être réalisée selon les indications ci dessous Calibres de câble recommandés pour...

Страница 7: ...les en utilisant les connecteurs et les techniques homologués NEC et UL appropriés 2 Pour les ensembles d alimentation électrique 20A et 30A branchez le cavalier Personality afin de sélectionner l élément chauffant 3 Réinsérez délicatement tous les fils et raccords dans la boîte de jonction Assurez vous qu il n y a aucune connexion desserrée ou fil non isolé exposé et épars 4 Placez le couvercle d...

Страница 8: ... à 4 voies dans la boîte de jonction 6 Replacez le couvercle de la boîte de jonction et réinstallez les trois vis retirées plus tôt AVIS La connexion des fils doit correspondre à l illustration ci dessus Les câbles d alimentation électrique du bâtiment et les fils du cordon d alimentation doivent tous être orientés verticalement et attachés avec une attache de câble 1 RETRAIT DU COUVERCLE DE LA BO...

Отзывы: