Configuration mode.
The configuration mode is used to set the RAK148P2 and RAK164P2
to match the heating/cooling system. These thermostats function
with up to 2-stage heat pump systems (RAK148P2 only).
To configure the RAK148P2 and RAK164P2, perform the
following steps:
Note:
Operation being set will blink in the display.
1.
Slide the
Function
switch to the
OFF
position.
2.
Simultaneously hold the
<
and
>
buttons in
for 6 seconds while the thermostat is in
OFF
mode.
3.
Press the
<
or
>
button to change settings within
each screen.
4.
Press the
Hold
button to advance to the next screen.
Note:
The
Mode
button will return you to the previous screen.
5.
To save the changes and exit configuration mode, slide the
Function
switch to
Heat
or
Cool
.
Configuration Mode Settings
The setup screens for Configuration Mode are as follows:
1.
7HPSHUDWXUH6FDOH)RU&³
Choose
Fahrenheit or Celsius.
Press
the
<
or
>
button
to select.
Press
the
Hold
button to advance to the next screen.
NOTE:
Default factory setting is Fahrenheit
.
2.
7HPSHUDWXUH'LIIHUHQWLDO³6WDJH³
(1–9°F) (1–5°C)
Set the number of degrees between the
“setpoint” temperature and the
“turn on” temperature for first stage.
Press
the
<
or
>
button to set differential value.
Press
the
Hold
button to advance to the next screen.
Note:
Default factory setting is 2°F/1°C for each stage.
8
: