1

CRITICAL DIMENSIONS

NOTE:

Care should be taken in location of electrical supply 

entry in relationship to wall sleeve to ensure access  

to power once the unit is installed.

31-30779-1

   

02-16 GE

INSTALL CASE LEVEL IN ALL DIRECTIONS

NOTES:

  Handle the case carefully.

  The cardboard stiffener inside the case, and the rear 

protective panel must remain in place until the chassis 

is installed to assure case rigidity and squareness.

  If a sub-base is to be used, it may be desirable to 

assemble it to the case before securing the case  

in the wall.

CASE LOCATION

Case must be located on an outside wall for proper 

operation.  As a general rule the air conditioner 

should be centrally located in an outside wall to 

ensure proper distribution of conditioned air. It should 

be located in a portion of the wall where there is no 

electrical wiring or plumbing, and where there are no 

obstructions immediately inside or outside.

For further details, refer to the GE Architects & Engineers Design Data Manual for Zonelines. To obtain a copy of that 

manual, call the GE Answer Center

®

 at 

800.626.2000

 or visit us at 

www.Zoneline.com

.

Ceiling

“A”

“B”

“C”

Roomside

Outside wall

“D”

Finished floor or top of carpet

Outside wall

“E”

“E”

Top of case

Printed in the United States

  

RECOMMENDED 

 DIMENSIONS 

INSTALLATION  CLEARANCE

 

A

7RSRIFDVHWRILQLVKHGFHLOLQJ³

s

 min.

 

B

 

Projection of case into room from finished  

 

 

wall - 1/4

s

 min. (no sub-base) 

 

 

2

ø

8

s

 min. when sub-base is used. 

 

 

If more than 6

s

 of the case projects 

 

 

into the room, a sub-base or other 

 

 

support is recommended.

 

C

3URMHFWLRQRIFDVHWRRXWVLGH³

s

 min.

 

D

 

Height above finished floor or  

WRSRIFDUSHW³

 

 

 

0

s

 min. without sub-base  

s

 min./5” max. with sub-base

 

E

 

Left/Right side of case to adjacent  

 

ZDOO³

s

 min.

Installation Instructions

for your new

Before you begin - Read these instructions completely and carefully.

IMPORTANT – OBSERVE ALL GOVERNING CODES AND ORDINANCES. 

Note to Installer – Be sure to leave these instructions with the Consumer. 

Note to Consumer – Keep these instructions with your Owner’s Manual for future reference.

RAB71B Standard 

or RAB7116B & 

RAB7124B

Extended Room Air Conditioner Case 

for AZ Series Zoneline Models Only

Содержание RAB71B Standard

Страница 1: ...Design Data Manual for Zonelines To obtain a copy of that manual call the GE Answer Center at 800 626 2000 or visit us at www Zoneline com Ceiling A B C Roomside Outside wall D Finished floor or top...

Страница 2: ...ase angles are to be used and must be installed proceed as follows 1 Position the case angles around top and sides of the case at the desired location front to rear with angles facing toward rear outs...

Страница 3: ...he case for electrical connections See the Zoneline Air Conditioner Owner s Manual for instructions on how to connect the electrical supply STEP 4 Weatherproofing Weatherproof gaps between the exterio...

Страница 4: ...8V Provisions should be made to have the proper electrical outlet near the case All wiring should be made in accordance with local codes and regulations The line cord included with the chassis if used...

Страница 5: ...du mur ne comportant aucun c blage lectrique ou tuyau de plomberie et ne pr sentant aucune obstruction imm diatement l int rieur ou l ext rieur Pour de plus amples renseignements reportez vous au docu...

Страница 6: ...t es localement proc dez de la fa on suivante 1 3ODFH OHV FRUQLqUHV VXU OH GHVVXV HW OHV F WpV GX ERvWLHU j O HQGURLW YRXOX GH O DYDQW YHUV O DUULqUH OHV DQJOHV IDLVDQW IDFH j O DUULqUH GX ERvWLHU H W...

Страница 7: ...Ne percez pas de trous dans le bo tier pour les raccordements lectriques Pour des directives sur OD IDoRQ G H HFWXHU OHV UDFFRUGHPHQWV pOHFWULTXHV reportez vous au Manuel d utilisation du climatiseur...

Страница 8: ...ent dans une prise de courant murale expos e 3RXU H HFWXHU OH UDFFRUGHPHQW j OD VRXUFH d alimentation lectrique reportez vous au Manuel d utilisation 4 ALIMENTATION LECTRIQUE 230 V 208 V Il faut pr vo...

Страница 9: ...donde no haya cableado el ctrico o tuber as de agua y donde no haya obstrucciones cercanas ya sea adentro o afuera Para mayores detalles consulte el Manual de informaci n de dise o para arquitectos e...

Страница 10: ...e la siguiente manera 1 Coloque los ngulos de la caja alrededor de la parte superior y los lados de la caja en la ubicaci n deseada de parte frontal a trasera con los ngulos orientados hacia atr s afu...

Страница 11: ...anual del propietario del acondicionador de aire Zoneline con instrucciones sobre c mo conectar el suministro el ctrico PASO 4 Resistencia a la intemperie Deben sellarse con calafateo o un material eq...

Страница 12: ...permite enchufar una unidad de 265V directamente en un tomacorriente expuesto montado en el edificio Ver el Manual del propietario sobre c mo conectar el suministro el ctrico 4 REQUERIMIENTOS EL CTRI...

Отзывы: