background image

2

 

GE is a registered trademark used under license from General Electric company

 

 

 

DEH4

02

28

 R

0

2 06 2

0

 

 

ABB Inc.

 

305 Gregson Drive Cary, NC 27511

 

 

8. Wire Main, Neutral, and Equipment Ground 

Refer  to  the  rating  label  inside  the  equipment  for  the 

proper  tightening  torques.  Wire  the  neutral  and 

equipment  grounds  only  in  the  directions  indicated  by 

the  arrows  in  the  figure  below.  Equipment  ground  is 

included. 

 

9. Optional Wiring of Neutral and Ground 

For  panelboards  rated  at  150  A  or  less,  the  neutral 

crossbar may be removed to provide optional neutral and 

ground wiring as follows: 

Left  side

 

  Insulated  neutral  or  ground  without  bonding 

strap.  Uninsulated  neutral  or  ground  with  bonding 

strap provided. 

Right side

 

 Insulated neutral or ground only. No bonding 

provision provided. Neutral terminal A may be moved 

to  left  side  or  see  rating  label  wiring  diagram  for 

additional terminal kit. 

NOTE:

 

If the load center is main breaker type and is not 

intended  for  service  entrance  use,  remove  the  bonding 

strap. 

10. Reinstall Service Entrance Barrier 

Reinstall the service entrance barrier removed in step 2. 

Secure the barrier with the two mounting screws. 

11. Wire Branch Circuits 

Individually wire each branch circuit into a circuit breaker, 

then plug the breaker into the interior. Refer to the label 

on the breaker for the proper tightening torque. Use GE 

circuit breakers only. 

 
 
 
 
 
 

 

 

12. Remove Cover Knockouts 

Place a screwdriver as shown and tap with a hammer. 

 

13. Important 

Retighten all electrical connections before energizing the 

load center. 

14. Screw Front on Box 

The adjustment for a flush mount is automatic when the 

cover is installed. 

15. Identify Circuits 

Use the labels provided to identify circuits for the user’s 

convenience. 

NOTE:

 

Accessories  and  replacement  parts  are  listed  on 

the label inside the load center. 

 

These instructions do not cover all details or variations 

in  equipment,  nor  do  they  provide  for  every  possible 

contingency  that  may  be  met  in  connection  with 

installation,  operation,  or  maintenance.  Should  further 

information  be  desired,  or  should  particular  problems 

arise that ar

e not covered sufficiently for the purchaser’s 

purposes,  the  matter  should  be  referred  to  ABB 

Company. 

 

 

 

Neutral 

Terminal A 

Insulated 

Ground or 

Neutral 

Equipment 

Ground 

Uninsulated 

Ground or 

Neutral 

Crossbar 

Bond 

Strap 

For troubleshooting or service related questions, 

https://electrification.us.abb.com/products/load-

centers

 

 

Содержание PowerMark Plus DEH40228

Страница 1: ...arton to protect the finish 2 Remove Service Entrance Barrier Main Breaker only Back out and save the two mounting screws securing the service entrance barrier over the main breaker connections then lift the barrier up and out 3 Remove Interior Optional Back out the mounting screws and save them for reuse 4 Mount Box Flush mount Line up the front box edge with the finish wall surface and screw or ...

Страница 2: ... barrier with the two mounting screws 11 Wire Branch Circuits Individually wire each branch circuit into a circuit breaker then plug the breaker into the interior Refer to the label on the breaker for the proper tightening torque Use GE circuit breakers only 12 Remove Cover Knockouts Place a screwdriver as shown and tap with a hammer 13 Important Retighten all electrical connections before energiz...

Страница 3: ...joncteur principal seulement Dévisser et conserver les deux vis de montage retenant la barrière de l entrée de service par dessus les connexions du disjoncteur principal puis soulever la barrière par en haut et l enlever 3 Enlever l interieur facultatif Retirer les vis de montage et les conserver pour les réutiliser 4 Monter la boîte Montage encastré aligner le côté devant de la boîte avec la surf...

Страница 4: ...nstaller la barrière de l entrée de service retirée à l étape 2 Fixer la barrière avec les deux vis de montage 11 Câbler les circuits de dérivation Câbler individuellement chaque circuit de dérivation à un disjoncteur puis le brancher à l intérieur Vous référer à l étiquette sur le disjoncteur pour un couple de serrage approprié N utiliser que des disjoncteurs GE 12 Enlever les débouchures du couv...

Отзывы: