OPM_GTU_19X_1K0_3K0_XUS_V014

 

7

 

GT-UL Series: User manual 1.2 (US)

 

Digital Energy

 

GT Series

g

 

 

 

 

2.4 Installation 

 

The unit should be installed by service personnel. 

 

IMPORTANT

Before making any connection and switching on the UPS, please check the following 

conditions: 

  Mains supply is 100/110/120 Volts and 50/60Hz, 

  Total power demand of the connected equipment does not exceed the rated output 

power of the UPS (indicated on the rating label). 

 

2.4.1  Mounting in a 19” enclosure 

 

1.  Install the mounting bracket. See fig. 2.2. 

2.  Adjust the rails and gently slide UPS into the rails. See fig. 2.3. 

3.  Fix mounting bracket on the enclosure by screws. See fig. 2.3. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.4.2 Vertical 

installation 

 

The UPS is rack mountable as well as 

standing alone. You can mount the UPS 

on the shelf, or you can erect the UPS 

with supporting stands (not included in 

delivery) as shown in fig 2.4.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig 2.2  Installing the mounting brackets 

Fig 2.3  Mounting the UPS 

Fig 2.4  Vertical installation

Supporting stands 
(not included) 

Содержание Power Supply

Страница 1: ...ower Supply 1000 1500 3000 VA UL version GE Consumer and Industrial Power Quality Digital Energy 701 E 22nd Street Suite 300 Telephone 800 637 1738 Lombard IL 60148 USA Website www geindustrial com up...

Страница 2: ...power failures Please keep this manual in a safe place for future reference and carefully read the important safety instructions in chapter 1 before installation and start up of the UPS 2007 by GE Co...

Страница 3: ...er available 3 2 2 Start up utility power not available cold start or battery start 3 3 Use Normal Operation 3 3 1 Normal operation conditions 3 3 2 Normal operation indications 3 3 3 UPS self test 3...

Страница 4: ...ing maintenance or service work The UPS contains potentially hazardous voltages 1 3 Installation The unit should be installed by service personnel To reduce the risk of electric shock install this UPS...

Страница 5: ...t charging source prior to connecting or disconnecting battery terminals Determine if the battery is inadvertently grounded If inadvertently grounded remove source of ground Contact with any part of a...

Страница 6: ...nterface cables when connecting to computer or peripheral devices Any changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate...

Страница 7: ...UPS 4 Output circuit breaker Protects the UPS from damage caused by output overload 5 DC connector To connect external battery pack for extended runtime 6 Fan Electronically controlled cooling fan Ma...

Страница 8: ...r of the UPS indicated on the rating label 2 4 1 Mounting in a 19 enclosure 1 Install the mounting bracket See fig 2 2 2 Adjust the rails and gently slide UPS into the rails See fig 2 3 3 Fix mounting...

Страница 9: ...RS232 dry contact interface Connect the interface signal cable between the RS 232 dry contact port on the rear panel of UPS and COM1 or COM2 of your computer if necessary See fig 2 6 Refer to chapter...

Страница 10: ...batteries the internal energy reserve were fully charged when the UPS left the factory they might have lost some energy during transport and or storage It is recommended to allow the UPS to recharge...

Страница 11: ...ting in the normal ON LINE mode 6 LED On Battery The UPS is operating in ON BATTERY back up mode utility power fails and the internal batteries supply the required power until either they are depleted...

Страница 12: ...ges the batteries 3 3 Use Normal Operation 3 3 1 Normal operation conditions The utility power supply is present and within allowable tolerances The load does not exceed the nominal rating of the UPS...

Страница 13: ...beeps with a 2 seconds interval When the utility power returns the UPS will switch back to normal operation In case of a long power failure the UPS will stop operating when the batteries have been dep...

Страница 14: ...the UPS functions under overload or over temperature conditions it may not be able to protect the load 3 4 5 Replace battery The batteries are aged and must be replaced as soon as possible to ensure...

Страница 15: ...or need a special UPS monitoring software For specific information on GE Digital Energy connectivity products please contact your local dealer 1 800 637 1738 The dry contacts 4 3 and optional SNMP plu...

Страница 16: ...at Hardware Baud rate 2400 bps Data length 8 bits Stop bit 1 bit Parity none Cabling Standard sub D 9 cable UPS side male PC side female 4 3 Dry Contact Its major functions are some or all of the foll...

Страница 17: ...otocol you can use browser Microsoft IE or Netscape Communicator to monitor or configure the UPS Besides the SNMP card supports Telnet and FTP for remote monitoring and firmware upgrading Specificatio...

Страница 18: ...teries General The service life of the battery is from 3 to 6 years depending on the operating conditions mainly temperature and number of discharge cycles As a healthy battery is critical to the perf...

Страница 19: ...4 Unscrew two bolts 5 6 Remove stop holder and battery terminal 7 Grasp the tag to pull out the battery sets Be careful heavy weight Notice not to let the battery set to drop in accident 7 When you s...

Страница 20: ...ow UPS to cool down Utility failure battery depleted Wait until utility power returns Input breaker tripped See above LED Fault lights up buzzer sounds continuously Internal UPS failure Contact your d...

Страница 21: ...ins Battery Recharge Time 4 6 hours after complete discharge to recover 90 Transfer Time Transfer Time zero LED Status On line Bypass On battery Overload Battery Low Fault Battery Replace Battery Leve...