Returning the Breaker to Service
28.
Replace the cover on the breaker according to the
instructions in GEH-4693 (800–2000 A) or GEH-4694
(2500–4000 A).
29.
For a draw-out installation, reinstall the side plate on
the breaker.
30.
Test the breaker at high current with primary current
injection before returning it to service.
31.
Reinstall the breaker into its cubicle or substructure.