background image

12. 

Install the new auxiliary switch [4] as follows: 
• 800–2000 A breaker: Insert the new switch into the 

breaker base and secure with the two screws [2] 

supplied, as shown in Figure 10. 

• 2500–4000 A breaker: Place the new switch over the 

C phase contact assembly and secure with the bolt, 

lock washer, and flat washer removed in the 

previous step, as shown in Figure 11. Tighten the 

bolt to 180–250 in.-lb. 

In both cases, use small wire ties [5] to dress the wire 

bundles. 

13. 

Insert the two white wires in the small auxiliary 

switch cable into the trip unit plug in positions 31 

and 34 (see the wiring diagram in Figure 6), as 

shown in Figure 12. 

14. 

File three slots in the breaker base, as shown in 

Figure 13, to accommodate the auxiliary switch wires. 

15. 

Run the five remaining auxiliary switch cables out 

through the slots in the breaker base. Secure the 

cables in position with large wire ties [6] for strain 

relief, as shown in Figure 14. 

 

Figure 10. New auxiliary switch [4] installed in an 800–2000 A 

breaker. 

 

Figure 11. New auxiliary switch [4] installed in a 2500–4000 A 

breaker. 

 

Figure 12. Auxiliary switch wires inserted into the trip unit plug. 

Auxiliary Switch 

Wires to Trip 

Unit Plug 

 

Figure 13. Filing slots in the breaker base for exit of the auxiliary 

switch wires (2500–4000 A shown). 

 

Figure 14. Auxiliary switch wires exiting the breaker (2500–4000 A 

shown). 

Wire Exit 

Slots 

Trip Unit 

Wires

Large Wire 

Tie [6] 

Small Wire 

Tie [5] 

Small Wire 

Tie [5] 

Содержание Power Break

Страница 1: ...8 TDOSVD907F Trip unit disconnect breaker 1 9 TDOSVD12 Trip unit disconnect substructure 1 10 Incl with 9 Spring 1 Table 3 List of parts in the power management upgrade kit for 800 2000 A draw out br...

Страница 2: ...re that the two nuts in the slots in the top of the CT don t fall out 9 Use pliers to bend the two locking tabs that secure the large plug to the trip unit mounting plate as shown in Figure 4 Slide th...

Страница 3: ...is present in a 2500 4000 A breaker remove and save the inner bolt lock washer and flat washer on the C phase contact assembly as shown in Figure 9 3 Figure 6 Wiring diagram for terminal board and tri...

Страница 4: ...own in Figure 12 4 14 File three slots in the breaker base as shown in Figure 13 to accommodate the auxiliary switch wires 15 Run the five remaining auxiliary switch cables out through the slots in th...

Страница 5: ...ure 18 Use small wire ties 5 as shown to dress the wire bundles 19 Slide the mounting bracket onto the large trip unit plug and slide the bracket over the two pins on the trip unit mounting plate as s...

Страница 6: ...forming screws 7 supplied as shown in Figure 23 Run the wires through the hole in the plate to the terminal board 24 Connect the wires from the breaker mounted trip unit disconnect 8 to the terminal...

Страница 7: ...05 106 red white blue power management 3 7 10 107 108 109 black red power management 4 8 110 111 Table 5 Wire groupings from the trip unit disconnect Spring Mounting Hole Figure 25 Placing the trip un...

Страница 8: ...o its cubicle or substructure g These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with installatio...

Отзывы: