PACSystems RXi IPC QSG

  

 

 

GFK-2784J

 

 
 
 

Power On/Off Switch and Status Indicator Operation 

Normal Operation

  Action 

Power up the IPC 

Press and hold the button for at least ½ second. 
If powering up from a no-power state, the ring LED blinks blue while the IPC is booting and is solid green 

when the IPC is up and running. 
If the system has been shut down, but power has not been cycled, the ring LED blinks blue for 40 seconds 

before changing to solid green. 

Shut down the IPC 

Press and hold the button briefly (between 100ms and 4 sec). 
The ring LED stays green while the IPC is shutting down, then turns off when the IPC is powered down. 

Sleep Mode 

The default BIOS settings when shipped from the factory are: 

 

Enable Hibernation is disabled 

 

ACPI Sleep State is S1 (CPU Stop Clock) 

The default settings send IPC to sleep state S1. 
The ring LED stays green while the IPC is in Sleep State S1.  
The ring LED fades blue while the IPC is in Sleep State S3. 

Forced Shut down 

Caution

:

 Use this option only if the operating system is non-responsive. 

Press the button for at least 4 seconds. 
The ring LED turns off.

 

The ring LED displays solid red to indicate a fault, including overtemp condition.

 

 

IPC Status Indicators Operation 

Indicator 

State 

Description 

SATA Drive Status 

 

White, blinking 

Read/write access on SATA drive 

Overtemp 

 

Red, solid 

The IPC’s internal temperature has exceeded the maximum allowable value. 
To recover, let the IPC cool, then press the Power On/Off switch. 

 

Ethernet Port LEDs Operation 

Each Ethernet port has two LED indicators, 

ACTIVITY

 and 

LINK

.  

 

LED 

LED State 

Operating State 

ACTIVITY

 

 

Blinking, Green 

Traffic is detected at the port 

LINK 

 

On, Green 

Link is operational 

 

 

 

 

Содержание PACSystems RXi ICRXIBN7E001A

Страница 1: ...rnal disks provide highly reliable local long term data retention USB and SD Card interfaces enable program loading serial communications and removable data storage through standard devices Ordering I...

Страница 2: ...mental Specifications Note The Box IPC should be installed in a location that is not exposed to corrosive gases or liquids rain or direct sunlight and meets the environmental specifications listed in...

Страница 3: ...should it be necessary to transport or ship any part of the system Note For phone numbers and email addresses refer to the section Contact Information Verify that all components of the system have be...

Страница 4: ...damage has been caused by incorrect transportation operating storage conditions or handling To power up the unit press the Power On Off switch for at least second If you notice any damage remove powe...

Страница 5: ...o shut down the IPC 1 Press the Power On Off switch briefly between 100 ms and 4 sec or select Shut Down from the Windows Start menu This provides a controlled shutdown of the operating system before...

Страница 6: ...Connector Indicators Connectors Blue blinking Booting Blue slow fade S3 Sleep Green solid Running Red solid Fault R e s e r v e d R e s e r v e d R e s e r v e d S A T A D r i v e S t a t u s O v e r...

Страница 7: ...CPI Sleep State is S1 CPU Stop Clock The default settings send IPC to sleep state S1 The ring LED stays green while the IPC is in Sleep State S1 The ring LED fades blue while the IPC is in Sleep State...

Страница 8: ...Customer Care Email customercare ip ge com Primary language of support English Europe the Middle East and Africa Online Technical Support http support ge ip com Phone 800 1 433 2682 EMEA Direct Dial...

Отзывы: