PACSystems RXi IPC QSG
2
General Specifications
Item
Specification
Dimensions
IPC: 191.8 x 115.6 x 81.3 mm (7.55 x 4.55 x 3.2 in)
Backplate: 226 x 137 x 12 mm (8.90 x 5.39 x 0.47 in)
Weight
IPC: 1.814 Kg (4 lbs)
Backplate: 0.454 Kg (1 lb)
Processor
1.0 GHz VIA Eden dual core processor
RAM
4 GB DDR3
Floating point
64 bit
Non-volatile storage
32 GB mSATA SSD or 250 GB SATA drive
Non-volatile storage (NVS) can retain data indefinitely without loss of data integrity
Time of day clock (RTC) accuracy
Maximum drift of ±2 seconds/day at 25°C (77 °F)
Elapsed time clock
(internal timing) accuracy
± 0.01% maximum
Video
Standard 15-pin VGA connector
Maintenance ports
(
Intended only for temporary connection)
Two Type A USB 2.0 SD standard card slot
Dual function Audio out/Microphone in jack (3.5 mm four-pin TRRS)
Power requirements
1.8 A at 24 VDC (18–32 VDC)
LPS or Class 2 power supply required
Serial Communications
One RS-232 RJ-45 port
Ethernet Communications
Two Ethernet (10, 100, 1000 Mbit/s) RJ-45 ports
Environmental Specifications
Note:
The Box IPC should be installed in a location that is not exposed to corrosive gases or liquids, rain, or direct sunlight,
and meets the environmental specifications listed in the following table.
Vibration
1
IEC60068-2-6
10 - 57 Hz, 0.006 in displacement peak-peak
57 - 500 Hz, 1.0 g acceleration
Shock
IEC60068-2-27
15 g, 11ms
Ambient Operating Temperature
2
-
ICRXIBNxE001A
3
: -25 to +65
°
C: [inlet] (-13 to 149 °F)
ICRXIBNxM001A: 0 to +40
°
C: [inlet] (32 to 104 °F)
Storage Temperature
-
-40 to +85
°
C (-40 to 185 °F)
Humidity
-
5 to 95%, non-condensing
Environment
UL60950-1
Pollution Degree 2
This applies where there is only non-conductive pollution that might
temporarily become conductive due to occasional condensation.
Altitude
UL60950-1
0–2000 m
1
Applies only to Box IPCs with solid state hard drive (ICRXIBNxE001A).
2
For ambient temperatures greater than 50°C (122 °F), the unit must be installed in a
restricted access area
as defined in this
document.
3
ICRXIBNxE001A may reduce its operating CPU frequency from 1.0 GHz to 800 MHz when operating at temperatures greater
than 60
°
C ambient. It will operate up to 65
°
C ambient as specified, but its performance will degrade based on the lower CPU
clock frequency.