Chapter 3. CPU Configuration
GFK-2222AD
April 2018
135
3.4.1
Establishing Initial Ethernet Communications
To establish Ethernet communications between the PME programming and configuration software and
the CPU, you
first
need to set an IP address. Use one of the following methods:
Default IP Addresses for RX3i
CPE302/CPE305/CPE310/CPE330/
CPE400
69
& RSTi-EP CPE100/CPE115
Embedded Ethernet
Initial Ethernet communication with the CPU may be established
using the default IP addresses programmed at the factory:
RX3i
CPE302/CPE305/
CPE310/CPE330/
CPE400 and RSTi-EP
CPE100/CPE115
LAN1
CPE330/CPE400
LAN2
RSTi-EP
CPE100/
CPE115
LAN2
IP
Address:
192.168.0.100
10.10.0.100
0.0.0.0
Subnet
Mask:
255.255.255.0
255.255.255.0
0.0.0.0
Gateway:
0.0.0.0
0.0.0.0
0.0.0.0
Connecting to CPE302/CPE305/
CPE310 Embedded Ethernet when
IP Addresses are not known
If the IP Address of the CPE302/CPE305/CPE310 embedded Ethernet
interface is not known, communication may be established using
one of these methods to set a permanent IP addresses:
•
Connect to the CPE302/CPE305/CPE310 via its serial port and
assign an IP Address to the embedded Ethernet interface by
downloading a hardware configuration.
•
Connect to the CPE302/CPE305/CPE310 with PME using an
IC695ETM001 module with a known IP address and located in
the same rack. Download a new hardware configuration with
the desired IP address for the embedded Ethernet interface.
Connecting to CPE330 Embedded
Ethernet when IP Addresses are not
known
If the IP Addresses of the CPE330 embedded LAN1 and LAN2
Ethernet interfaces are not known, communication may be
established using one of these methods to set new IP addresses:
•
Setting a Temporary IP Address
Set Temporary IP
Address
tool in Proficy Machine Edition (PME). After setting the
temporary address, connect to the selected CPE330 LAN using
PME and download a new hardware configuration with the
desired permanent IP addresses.
•
Connect to the CPE330 with PME using an IC695ETM001
module with a known IP address and located in the same rack.
Download a new hardware configuration with the desired
permanent IP addresses for the CPE330 embedded Ethernet
interfaces.
Connecting to CPE400 Embedded
Ethernet when IP Addresses are not
known
Use the OLED display to read the IP Address of any LAN.
Note:
CPE400.
69
CPE LAN3 IP Address is not configurable.