Chapter 5
.
Diagnostics
Bit#
Name
Bit
Condition Meaning of Status Bit
0
Module OK
OFF
The GCG001 module is powering up or has failed.
ON
Indicates the GCG001 module is functioning properly.
1
Fault Present
OFF
No GCG001 diagnosis data available; FAULT LED is Off.
ON
GCG001 diagnosis data is available; FAULT LED is On.
2
Port1 Link Up
OFF
Port is not connected to a properly configured device,
or port is experiencing communications errors.
ON
Port is connected to another device and is
communicating.
3
Port2 Link Up
OFF
Port is not connected to a properly configured device,
or port is experiencing communications errors.
ON
Port is connected to another device and is
communicating.
4-9
Reserved
OFF
Always off
ON
N/A
10
MRP Enabled
OFF
MRP is not enabled
ON
MRP is enabled
11
MRP Role
OFF
Indicates that the GCG001 is an MRP Client (if MRP is
enabled), or that MRP is not enabled.
ON
Indicates role is that of an MRP Manager – this is not a
possible role for the GCG001.
12-31
Reserved
OFF
Always off
ON
N/A
5.1.2
Genius Status Data
For the Genius Status Data, status bits are arranged in ascending order of the Genius Serial
Bus Addresses (SBAs), beginning at the first %I status reference assigned to this bank of 32.
Figure 22: Genius Status Data
Bit
Condition Meaning of Status Bit
OFF
No device present at SBA, or device not configured, or device not communicating.
ON
Device present, configured and communicating at corresponding SBA.
5.2
Module LED Indicators
Refer to Section 2.4.4 for a description of LED indications.
38
Public
PACSystems RX3i Genius Communications Gateway User Manual
GFK-2892B
Содержание PACSystems RX3i Genius
Страница 10: ...Contents Notes 6 Public PACSystems RX3i Genius Communications Gateway User Manual GFK 2892B ...
Страница 22: ...Chapter 1 Introduction Notes 18 Public PACSystems RX3i Genius Communications Gateway User Manual GFK 2892B ...
Страница 32: ...Chapter 2 Installation Notes 28 Public PACSystems RX3i Genius Communications Gateway User Manual GFK 2892B ...
Страница 48: ...Chapter 5 Diagnostics Notes 44 Public PACSystems RX3i Genius Communications Gateway User Manual GFK 2892B ...