GE MVAX 11 Скачать руководство пользователя страница 10

 

 

 

 

 

 

 

 

 

 

Equipment operating conditions 

The equipment should be operated within the specified electrical 
and environmental limits. 

 

Current transformer circuits 
Do not open the secondary circuit of a live CT since the high 
voltage produced may be lethal to personnel and could damage 
insulation.  Generally, for safety, the secondary of the line CT must 
be shorted before opening any connections to it. 

For most equipment with ring-terminal connections, the threaded 
terminal block for current transformer termination has automatic CT 

shorting on removal of the module.  Therefore external shorting of 
the CTs may not be required, the equipment documentation should 
be checked to see if this applies. 

For equipment with pin-terminal connections, the threaded terminal 
block for current transformer termination does NOT have automatic 
CT shorting on removal of the module. 

 

External resistors, including voltage dependent resistors (VDRs) 
Where external resistors, including voltage dependent resistors 

(VDRs), are fitted to the equipment, these may present a risk of 
electric shock or burns, if touched. 

 

Battery replacement 
Where internal batteries are fitted they should be replaced with the 
recommended type and be installed with the correct polarity to 
avoid possible damage to the equipment, buildings and persons. 

 

Insulation and dielectric strength testing 
Insulation testing may leave capacitors charged up to a hazardous 

voltage.  At the end of each part of the test, the voltage should be 
gradually reduced to zero, to discharge capacitors, before the test 
leads are disconnected. 

 

Insertion of modules and pcb cards 
Modules and PCB cards must not be inserted into or withdrawn from 
the equipment whilst it is energized, since this may result in damage. 

 

I

nsertion and withdrawal of extender cards

 

Extender cards are available for some equipment.  If an extender 
card  is  used,  this  should  not  be  inserted  or  withdrawn  from  the 
equipment whilst it is energized.  This is to avoid possible shock or 
damage hazards.  Hazardous live voltages may be accessible on 
the extender card. 

 

External test blocks and test plugs

 

Great care should be taken when using external test blocks and test 
plugs such as the MMLG, MMLB and MiCOM P990 types, hazardous 
voltages may be accessible when using these.  *CT shorting links 
must be in place before the insertion or removal of MMLB test plugs, 
to avoid potentially lethal voltages. 

*Note: When a MiCOM P992 Test Plug is inserted into the MiCOM 

Содержание MVAX 11

Страница 1: ...GE Grid Solutions MVAX 11 12 21 31 91 Technical Manual Trip Circuit Supervision Relay Publication reference R8010RB ...

Страница 2: ......

Страница 3: ...SAFETY SECTION ...

Страница 4: ......

Страница 5: ...ondition It is assumed that everyone who will be associated with the equipment will be familiar with the contents of this Safety Section or the Safety Guide SFTY 4L M When electrical equipment is in operation dangerous voltages will be present in certain parts of the equipment Failure to observe warning notices incorrect use or improper use may endanger personnel and equipment and also cause perso...

Страница 6: ...r the manuals cannot cover all conceivable circumstances or include detailed information on all topics In the event of questions or specific problems do not take any action without proper authorization Contact the appropriate General Electric technical sales office and request the necessary information ...

Страница 7: ...tion Caution risk of electric shock Protective Conductor Earth terminal Functional Protective Conductor Earth terminal Note This symbol may also be used for a Protective Conductor Earth terminal if that terminal is part of a terminal block or sub assembly e g power supply NOTE THE TERM EARTH USED THROUGHOUT THIS TECHNICAL MANUAL IS THE DIRECT EQUIVALENT OF THE NORTH AMERICAN TERM GROUND 3 2 Labels...

Страница 8: ...e device General Electric strongly recommends that these contacts are hardwired into the substation s automation system for alarm purposes To ensure that wires are correctly terminated the correct crimp terminal and tool for the wire size should be used The equipment must be connected in accordance with the appropriate connection diagram Protection Class I Equipment Before energizing the equipment...

Страница 9: ...current rating of external wiring applicable to the application Accidental touching of exposed terminals If working in an area of restricted space such as a cubicle where there is a risk of electric shock due to accidental touching of terminals which do not comply with IP20 rating then a suitable protective barrier should be provided Equipment use If the equipment is used in a manner not specified...

Страница 10: ...ries are fitted they should be replaced with the recommended type and be installed with the correct polarity to avoid possible damage to the equipment buildings and persons Insulation and dielectric strength testing Insulation testing may leave capacitors charged up to a hazardous voltage At the end of each part of the test the voltage should be gradually reduced to zero to discharge capacitors be...

Страница 11: ...Service Manual R8010RB MVAX Page 1 24 TYPE MVAX TRIP CIRCUIT SUPERVISION RELAY ...

Страница 12: ......

Страница 13: ...7 4 MVAX 31 MVAX 91 3 separate MVAX 31 s in a size 8 case 9 2 7 5 MVAX 31 04 only 10 2 7 6 MVAX 31 with CCT breaker closure inhibit contact 11 3 MAINTENANCE 13 4 MECHANICAL SETTINGS 13 4 1 General 13 4 1 1 With the armature closed the clearance between the back of the armature and the back stop should be 0 075 0 2mm 0 003 0 008 13 4 1 2 Nominal armature gap open 13 4 2 Contact settings 14 4 2 1 MV...

Страница 14: ...m trip supervision relay 16 Figure 2 Supervision of interposing control relay type MVAW 17 Figure 3 Supervision of tripping relay type MVAJ 17 Figure 4 Circuit diagram MVAX21 trip circuit supervision relay without preclosing supervision 18 Figure 5 Application diagram MVAX21 trip circuit supervision relay without preclosing supervision 19 Figure 6 Circuit diagram MVAX31 trip circuit supervision re...

Страница 15: ...which are being carried out at the same time as constructional work Storage If relays are not installed immediately upon receipt they should be stored in a place free from dust and moisture in their original cartons and where de humidifier bags have been included in the packing they should be retained The action of the de humidifier crystals will be impaired if the bag has been exposed to ambient ...

Страница 16: ...release On units fitted with hand reset flag indicators check that the flag is free to fall before or just as any make contacts close Replace the module in the case and refit the cover Make sure that the reset mechanism in the cover is correctly located with respect to the relay element and that the flag or mechanism can be reset 2 2 Wiring Check that ratings of the relay agree with the supplies t...

Страница 17: ...is within those figures stated in the same column Repeat again only using terminals 27 28 Rated voltage range V 30 34 48 54 110 125 120 250 Test voltage V 30 48 110 220 Terminals 21 27 46 1 56 3mA 24 1 29 5mA 11 13 4mA 11 4 14mA Terminals 27 28 46 1 56 3mA 24 1 29 5mA 11 13 4mA 11 4 14mA 2 7 2 MVAX 12 only Isolate the relay from the trip supply batteries by removing fuses links as necessary Using ...

Страница 18: ...rm supply voltages immediately prior to the tests and note Test 1 With the circuit breaker open check that no voltage appears across terminals 13 and 14 of the relay Check that the voltage appearing across terminals 21 and 28 comply with that given in Table 1 alarm supply and that the front relay RL1 has operated Reset its flag Test 2 With the circuit breaker closed check that the front relay rema...

Страница 19: ...e of the relay The same voltage limits apply Both these voltages are derived from the trip supply Check the voltage across terminals 27 and 28 ve of the relay This should be within the limits given in Table 2 for the alarm supply Note that the front relay unit RL1 is picked up and reset its flag Test 3 With the circuit breaker closed check that the front relay RL1 remains operated Check that no vo...

Страница 20: ... For other voltages within the relays normal voltage rating range tolerance bands for other measured supply voltages should be altered pro rata A Table Table 1 of acceptable tolerance for the test is given Measure the trip supply and alarm supply voltages immediately prior to tests and note Test 1 With the circuit breakers open check that no voltage appears across terminals 13 and 14 21 and 22 of ...

Страница 21: ...limits apply Both these voltages are derived from the trip supply Check the voltage across terminals 27 and 28 ve of the relay This should be within the limits given in Table 3 for the alarm supply Note that the front relay unit RL1 is picked up and reset its flag Test 3 With the circuit breaker closed check that the front relay RL1 remains operated Check that no voltage appears across terminals 2...

Страница 22: ...ed on drop off to prevent mal operation during the transition period Relay V rating 110 125 Ref V for tolerance 125 Hand reset flag 25 8 31 6V Test 1 Trip supply Self reset flag 25 8 31 6V Hand reset flag 31 3 38 8V Test 2 Alarm supply Self reset flag 38 46 6V Hand reset flag 51 6 63 1V Test 3 Trip supply Self reset flag 51 6 63 1V Hand reset flag 7400 Test 4 Self reset flag 7400 Table 3 MVAX31 wi...

Страница 23: ...s In general contact gaps and follow through are defined by quoting an armature gap at which the tips should be just closed or just open The relay contact state is always defined with the relay in the unenergised position unless otherwise specified on the appropriate circuit diagram Symbol used on diagrams Contact Type Normal duty Make Normally open M Break Normally closed B 4 1 1 With the armatur...

Страница 24: ... break contacts 1 75 2mm 0 07 0 08 Note On MVAX 21 31 Relays To measure the force to just close or the force to just break on the lower right hand contact when viewed from the front of the module it is necessary to carefully lift the upper moving contact blade to remove the pressure on the lower contact 4 2 3 MVAX 21 Unit RL2 MVAX 31 Units RL2 and RL3 With the armature closed onto a 0 25mm 0 011 f...

Страница 25: ...cts not changing state Pushrod not in position Check output terminals with reference to diagram Contamination of contacts MVAX 21 31 91 Units RL2 RL3 contacts not closing 5 3 Reset time on MVAX 12 too short Check capacitor C1 is not open circuit or short circuit Contacts should be cleaned with the burnishing tool supplied in relay tool kits On no account should knives files or abrasive materials b...

Страница 26: ...rear Note 1 a b c Short terminals break before c Long terminals CT shorting links make before b and c disconnect Case earth Combinations of output contacts Output contacts to module terminals 1 3 2 4 M M M B B B 2M 2M 1M 1B 2B Contact descriptions M B Make Break Figure 1 Circuit and application diagram trip supply supervision relay ...

Страница 27: ...rposing control relay 1 3 2 4 MVAX 11 Supervisory relay P1077ENa Figure 2 Supervision of interposing control relay type MVAW R2 R1 Protective relay contact 27 28 21 MVAJ Tripping relay 1 3 2 4 MVAX 11 Supervision relay P1078ENa Figure 3 Supervision of tripping relay type MVAJ ...

Страница 28: ... 1 a b c Short terminals break before c Long terminals CT shorting links make before b and c disconnect 7 8 9 10 1 12 Case earth 3M Combinations of output contacts Output contacts to module terminals 1 3 5 7 M M B 2M 1B 1M 2B B 3B 2 4 M B B M M M B B V x V x Contact descriptions M B Make Break P1079ENa Figure 4 Circuit diagram MVAX21 trip circuit supervision relay without preclosing supervision ...

Страница 29: ...ip coil 27 28 R EXT 1 RL1 3 52 b C B aux switch Trip coil 21 RL2 1 Trip supply Vx 2 Alarm supply Vx 1 1 RL1 1 4 2 RL1 2 7 5 RL1 3 Note Contact arrangement shown is typical only Alarm contacts P1080ENa Figure 5 Application diagram MVAX21 trip circuit supervision relay without preclosing supervision ...

Страница 30: ...R8010RB Service Manual Page 20 24 MVAX P4066ENa Figure 6 Circuit diagram MVAX31 trip circuit supervision relay with preclosing supervision ...

Страница 31: ...Service Manual R8010RB MVAX Page 21 24 P4067ENa Figure 7 Application diagram MVAX31 trip circuit supervision relay with preclosing supervision ...

Страница 32: ...R8010RB Service Manual Page 22 24 MVAX P4068ENa ...

Страница 33: ...x2 V REXT2 ohms Alarm Vx1 V REXT1 ohms MVAX 31 91 Trip Vx2 V REXT2 3 ohms Commissioning preliminaries Tick if satisfactory Insulation tests Satisfactory Not required Test results MVAX 11 relay Test 2 7 1 Resistance across terminals 21 27 Ω 27 28 Ω Trip supply voltage V CB open Relay stable CB closed Relay stable Trip circuit open Relay operates Contacts checked Test results MVAX 12 relay Test 2 7 ...

Страница 34: ... Volts across terminals 13 and 14 V 3 tick 4 tick Test results MVAX 31 relay Test 2 7 4 Measured trip supply V alarm supply V 1 and 2 CB open Volts across terminals 13 and 14 V 21 and 22 V 27 and 28 V 3 CB closed 21 2 V 13 and 14 V 4 CB closed Resistance between 14 and 22 ohms 5 tick 6 tick Note For details of the above tests see Publication R8010 Comments Commissioning Engineer Customer Witness D...

Страница 35: ...iled during service Yes How long 2 SPECIALIST REPAIR INSTRUCTIONS Do you want an updated firmware version after repair Yes No Is the relay being returned in a case Yes No If No see repair Term 5 3 CUSTOMS INVOICING INFORMATION REQUIRED TO ALLOW RETURN OF REPAIREDITEMS Value for Customs M Customer Invoice Address if paid M Customer Return Delivery Address full street address M Part Shipment Accepte...

Страница 36: ...e box should be used with packing material at the bottom the device placed into box with sufficient gaps to fill with packing material around each side and on the top extra packaging material placed around therelay 4 Please include a copy of the completed RMA form then close the lid and seal with packaging tape 5 The relay should then be secondary packed if being exported the primary packed box sh...

Страница 37: ......

Страница 38: ...n this document is indicative only No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project This will depend on the technical and commercial circumstances It is provided without liability and is subject to change without notice Reproduction use or disclosure to third parties without express written authority is strictly pr...

Отзывы: