CHAPTER 4: PROGRAMMING
S2 SYSTEM SETUP
PQM POWER QUALITY METER – INSTRUCTION MANUAL
4–29
4.3.3
Analog Input
FIGURE 4–15: Setpoints Page 2 – System Setup / Analog Input
•
ANALOG IN MAIN/ALT SELECT RELAY:
Select the output relay that is to be used to
multiplex two analog input signals to the PQM.
If this setpoint is
OFF
, the MAIN analog
input setpoints will be used unless a switch input assigned to SELECT ANALOG INPUT is
activated. For more information on multiplexing two analog inputs using one of the
PQM output relays, refer to Section 2.2.6: Switch Inputs (Optional) on page –16.
•
ANALOG IN MAIN/ALT NAME:
This message allows the user to input a user defined 20
character alphanumeric name for the MAIN and ALT analog inputs. To enter the
names, perform the following steps:
1.Allow access to setpoints by enabling setpoint access.
2.Select the Analog Input name message display under the
S2 SYSTEM SETUP \ ANALOG INPUT
setpoints group.
]] SETPOINTS
]] S2 SYSTEM SETUP
]] SETPOINTS
]] S3 OUTPUT RELAYS
SETPOINT
] CURRENT/VOLTAGE
] CONFIGURATION
] ANALOG INPUT
]
ANALOG IN MAIN/ALT
SELECT RELAY: OFF
ANALOG IN MAIN NAME:
MAIN ANALOG INPUT
Range: AUX1, AUX2, A UX3, OFF
ANALOG IN MAIN
UNITS: mA
MAIN 4mA VALUE:
0
MAIN 20mA VALUE:
0
ANALOG IN MAIN RELAY:
OFF
] ANALOG OUTPUT 4
]
ANALOG IN MAIN LEVEL:
100
ANALOG IN MAIN
DELAY: 10.0 s
ANALOG IN ALT NAME:
ALT ANALOG INPUT
ANALOG IN ALT
UNITS:
ALT 4 mA VALUE:
0
ALT 20mA VALUE:
0
ANALOG IN ALT
RELAY: OFF
ANALOG IN ALT LEVEL:
100
ANALOG IN ALT
DELAY: 10.0 s
Range: 0 to 65000 ; Step: 1
Range:ALARM, AUX1,
AUX2, AUX3, OFF
Range: 0 to 65000 ; Step: 1
Range: 0 to 65000 ; Step: 1
Range: 10 alpha numeric
characters
Range: 20 alpha numeric
characters
Range: 0.5 to 600.0 s
Step: 0.5 s
Range: 0 to 65000
Step: 1
Range:ALARM, AUX1,
AUX2, AUX3, OFF
Range: 0 to 65000
Step 1
Range: 0 to 65000
Step: 1
Range: 20 alpha numeric
characters
Range: 10 alpha numeric
characters
Range: 0.5 to 600.0 s
Step: 0.5 s