2
MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE
CHAPTER 1: OVERVIEW
Table 1-1: MM300 protection functions
RS485 - Modbus RTU
Ethernet - Modbus TCP/IP
Profibus/DeviceNet
52
27
59
47
METERING
V, A, W, var, VA, PF, Hz
27X
51R
49
37
66
46
50G 51G
49
MOTOR
LOAD
Stator RTDs
Bearing RTDs
Phase CT 3
Ground CT 1
Power Fuse
BUS
MM300
MOTOR MANAGEMENT SYSTEM
Temperature
Thermistor
Control PT
Contactor
Control
fuse
Direct voltage inputs
(690 V AC maximum)
Ambient air
RTD
Expansion module,
two cards per module,
maximum of two modules
38
Optional
three-phase
voltage
card
Options:
Six
inputs
&
tw
o
form-A
outputs
(max
5
car
ds)
?
?
Thr
ee-phase
voltage
car
d
(max
1
car
d)
Options:
Thr
ee
R
TDs
-
100
ohm
Platinum
(max
2
car
ds)
?
?
F
our
form-C
contact
outputs
(max
4
car
ds)
853739A2.CDR
Six inputs and two outputs (standard)
Optional
R
T
D
car
d
ANSI device
Description
27X
Undervoltage, auxiliary input
27
Undervoltage, three-phase
37
Undercurrent and underpower
38
Bearing temperature RTD
46
Current unbalance
47
Voltage phase reversal
49
Thermal overload
50G
Ground instantaneous overcurrent
51G
Ground time overcurrent
51R
Locked/stalled rotor, mechanical jam
59
Overvoltage, three-phase
66
Starts per hour and time between starts
Содержание Multilin MM300
Страница 53: ...2 MM300 MOTOR MANAGEMENT SYSTEM QUICKSTART GUIDE ACTUAL VALUES OVERVIEW CHAPTER 3 ACTUAL VALUES...
Страница 61: ...8 MM300 MOTOR MANAGEMENT SYSTEM QUICKSTART GUIDE CONFIGURATION SETPOINTS CHAPTER 4 SETPOINTS...
Страница 67: ...2 MM300 MOTOR MANAGEMENT SYSTEM QUICKSTART GUIDE COMMUNICATIONS INTERFACES CHAPTER 6 COMMUNICATIONS...