9-14
MIGII Digital Protection for Electrical Machines
GEK-113188A
9.14 PHASE TOC ELEMENT (51P)
9 RELAY COMMISSIONING
9
9.14PHASE TOC ELEMENT (51P)
3 Available curves IEC or ANSI (Inverse, Very Inverse, Extremely Inverse) and the Definite Time are tested with three
points for each curve (one “no-trip point” and two “trip points”). This gives us a total of 12 points for each protection element.
Each point is tested with a different pick up and dial in order to test the whole range of the relay.
Enable 51P element only, and set its current pickup value to the minimum possible.
9.14.1 IEC INVERSE CURVE
Set the relay as follows:
Apply 0.9 times the pickup current into phase A and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 15.3 and 19.7 sec.
Apply 5 times the pickup current and the relay should trip between 4.1 and 4.5 sec.
9.14.2 IEC VERY INVERSE CURVE
Set the relay as follows:
Apply 0.9 times the pickup current into phase B and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 23.4 and 31.8 sec.
Apply 5 times the pickup current and the relay should trip between 3.1 and 3.6 sec.
9.14.3 IEC EXTREMELY INVERSE CURVE
Set the relay as follows:
Apply 0.9 times the pickup current into phase C and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 27 and 39 sec.
Apply 5 times the pickup current and the relay should trip between 1.5 and 1.85 sec.
51P SETTINGS GROUP
Curve
INVERSE
Time Dial
1
51P SETTINGS GROUP
Curve
VERY INVERSE
Time Dial
1
51P SETTINGS GROUP
Curve
EXTREMELY INVERSE
Time Dial
0. 5
Содержание Multilin MIGII
Страница 2: ......
Страница 114: ...5 24 MIGII Digital Protection for Electrical Machines GEK 113188A 5 4 TIME SYNCHRONIZATION 5 SETTINGS 5 ...
Страница 136: ...8 8 MIGII Digital Protection for Electrical Machines GEK 113188A 8 4 OPERATIONS 8 KEYPAD AND DISPLAY 8 ...
Страница 137: ...GEK 113188A MIGII Digital Protection for Electrical Machines 8 9 8 KEYPAD AND DISPLAY 8 4 OPERATIONS 8 ...
Страница 138: ...8 10 MIGII Digital Protection for Electrical Machines GEK 113188A 8 4 OPERATIONS 8 KEYPAD AND DISPLAY 8 ...
Страница 139: ...GEK 113188A MIGII Digital Protection for Electrical Machines 8 11 8 KEYPAD AND DISPLAY 8 4 OPERATIONS 8 ...
Страница 140: ...8 12 MIGII Digital Protection for Electrical Machines GEK 113188A 8 4 OPERATIONS 8 KEYPAD AND DISPLAY 8 ...
Страница 141: ...GEK 113188A MIGII Digital Protection for Electrical Machines 8 13 8 KEYPAD AND DISPLAY 8 4 OPERATIONS 8 ...
Страница 142: ...8 14 MIGII Digital Protection for Electrical Machines GEK 113188A 8 4 OPERATIONS 8 KEYPAD AND DISPLAY 8 ...
Страница 143: ...GEK 113188A MIGII Digital Protection for Electrical Machines 8 15 8 KEYPAD AND DISPLAY 8 4 OPERATIONS 8 ...
Страница 144: ...8 16 MIGII Digital Protection for Electrical Machines GEK 113188A 8 4 OPERATIONS 8 KEYPAD AND DISPLAY 8 ...
Страница 200: ...A 10 MIGII Digital Protection for Electrical Machines GEK 113188A A 6 MIGII THERMAL CURVES APPENDIXA A ...
Страница 208: ...B 8 MIGII Digital Protection for Electrical Machines GEK 113188A B 2 ANSI CURVES APPENDIXB B Figure B 4 ANSI INVERSE ...
Страница 230: ...C 20 MIGII Digital Protection for Electrical Machines GEK 113188A C 8 MODBUS MAP STATUS APPENDIXC C ...