B-40
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
66FA
Generator Unbalance Block
0 to 4294967295
---
1
F300
0
66FC
Generator Unbalance Target
0 to 2
---
1
F109
0 (Self-reset)
66FD
Generator Unbalance Events
0 to 1
---
1
F102
0 (Disabled)
66FE
Reserved (3 items)
0 to 65535
---
1
F001
0
Stator Ground Source (Read/Write Grouped Setting)
670A
Stator Ground Source
0 to 5
---
1
F167
0 (SRC 1)
Subharmonic Stator Ground (Read/Write Grouped Setting)
6710
Subharmonic Stator Ground Function
0 to 1
---
1
F102
0 (Disabled)
6711
Subharmonic Stator Ground Stage 1 Pickup
1 to 20
kOhm
1
F001
10
6712
Subharmonic Stator Ground Stage 1 Pickup Delay
0.1 to 600
s
0.1
F001
100
6713
Subharmonic Stator Ground Stage 2 Pickup
1 to 20
kOhm
1
F001
3
6714
Subharmonic Stator Ground Stage 2 Pickup Delay
0.1 to 600
s
0.1
F001
10
6715
Subharmonic CT Angle Compensation
-30 to 30
degrees
0.1
F002
0
6718
Subharmonic Stator Ground OC Pickup
0.001 to 1
pu
0.001
F001
10
6719
Subharmonic Stator Ground OC Delay
0.1 to 600
s
0.01
F001
100
671A
Subharmonic Stator Ground Volt Supv
0 to 0.1
pu
0.001
F001
0
671B
Subharmonic Stator Ground Curr Supv
0 to 0.1
pu
0.001
F001
0
671C
Subharmonic Stator Ground Block
0 to 4294967295
---
---
F300
0
671E
Subharmonic Stator Ground Events
0 to 1
---
1
F102
0 (Disabled)
671F
Subharmonic Stator Ground Target
0 to 2
---
1
F109
0 (Self-reset)
Stator Ground (Read/Write Grouped Setting)
6720
Stator Ground Function
0 to 1
---
1
F102
0 (Disabled)
6721
Stator Ground Stage 1 Pickup
0 to 0.9
pu
0.001
F001
150
6722
Stator Ground Stage 1 Pickup Delay
0 to 600
s
0.01
F001
100
6723
Stator Ground Stage 1 Supv
0.001 to 0.1
pu
0.0001
F001
57
6724
Stator Ground Stage 2 Pickup
0 to 0.9
pu
0.001
F001
150
6725
Stator Ground Stage 2 Pickup Delay
0 to 600
s
0.01
F001
0
6726
Stator Ground Stage 2 Supv
0.001 to 0.1
pu
0.0001
F001
45
6727
Stator Ground Block
0 to 4294967295
---
1
F300
0
6729
Stator Ground Target
0 to 2
---
1
F109
0 (Self-reset)
672A
Stator Ground Event
0 to 1
---
1
F102
0 (Disabled)
672B
Reserved (5 items)
0 to 65535
---
1
F001
0
Split Phase Protection (Read/Write Grouped Setting)
6730
Split Phase Protection Function
0 to 1
---
1
F102
0 (Disabled)
6731
Split Phase Protection Source
0 to 5
---
1
F167
0 (SRC1)
6732
Split Phase Protection Load Source
0 to 5
---
1
F167
0 (SRC1)
6733
Split Phase Protection Phase A Pickup
0.02 to 1.500
pu
0.001
F001
200
6734
Split Phase Protection Phase A Offset
0 to 1
pu
0.001
F001
0
6735
Split Phase Protection Phase A Slope
0 to 100
%
0.1
F001
0
6736
Split Phase Protection Phase B Pickup
0.02 to 1.500
pu
0.001
F001
200
6737
Split Phase Protection Phase B Offset
0 to 1
pu
0.001
F001
0
6738
Split Phase Protection Phase B Slope
0 to 100
%
0.1
F001
0
6739
Split Phase Protection Phase C Pickup
0.02 to 1.500
pu
0.001
F001
200
673A
Split Phase Protection Phase C Offset
0 to 1
pu
0.001
F001
0
673B
Split Phase Protection Phase C Slope
0 to 100
%
0.1
F001
0
673C
Split Phase Protection Minimum Load
0 to 1
pu
0.01
F001
0
673D
Split Phase Protection Mode
0 to 1
---
1
F225
0 (Over)
673E
Split Phase Protection Delay
0 to 65.535
s
0.001
F001
0
673F
Split Phase Protection Block
0 to 4294967295
---
1
F300
0
6741
Split Phase Protection Target
0 to 2
---
1
F109
0 (Self-Reset)
6742
Split Phase Protection Events
0 to 1
---
1
F102
0 (Disabled)
6743
Reserved (6 items)
0 to 65535
---
1
F001
0
Phase Undervoltage (Read/Write Grouped Setting) (3 modules)
7000
Phase Undervoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
Table B–10: MODBUS MEMORY MAP (Sheet 32 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...