5 SETTINGS
5.4 SYSTEM SETUP
5
•
PMU 1 POWER TRIGGER REACTIVE
: This setting specifies the pickup threshold for the reactive power of the
source. For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second-
ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin-
gle-phase power. The comparator applies a 3% hysteresis.
•
PMU 1 POWER TRIGGER APPARENT
: This setting specifies the pickup threshold for the apparent power of the
source. For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second-
ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin-
gle-phase power. The comparator applies a 3% hysteresis.
•
PMU 1 POWER TRIGGER PKP TIME
: This setting could be used to filter out spurious conditions and avoid unneces-
sary triggering of the recorder.
•
PMU 1 POWER TRIGGER DPO TIME
: This setting could be used to extend the trigger after the situation returned to
normal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the
triggering condition is asserted).
Figure 5–50: POWER TRIGGER SCHEME LOGIC
j) DF/DT TRIGGERING
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT...
PMU 1 TRIGGERING
PMU 1 df/dt TRIGGER
PMU 1 df/dt
TRIGGER
PMU 1 df/dt TRIGGER
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
PMU 1 df/dt TRIGGER
RAISE: 0.25 Hz/s
Range: 0.10 to 15.00 Hz/s in steps of 0.01
MESSAGE
PMU 1 df/dt TRIGGER
FALL: 0.25 Hz/s
Range: 0.10 to 15.00 Hz/s in steps of 0.01
MESSAGE
PMU 1 df/dt TRIGGER
PKP TIME: 0.10 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PMU 1 df/dt TRIGGER
DPO TIME: 1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PMU 1 df/dt TRG BLK:
Off
Range: FlexLogic operand
MESSAGE
PMU 1 df/dt TRIGGER
TARGET: Self-Reset
Range: Self-Reset, Latched, Disabled
MESSAGE
PMU 1 df/dt TRIGGER
EVENTS: Disabled
Range: Enabled, Disabled
847011A1.CDR
SETTINGS
PMU 1 POWER
TRIGGER FUNCTION:
Enabled = 1
PMU 1 PWR TRIG BLK:
Off = 0
AND
SETTINGS
PMU 1 POWER TRIGGER ACTIVE:
RUN
SETTINGS
PMU 1 POWER TRIGGER DPO TIME:
t
DPO
FLEXLOGIC OPERAND
PMU 1 POWER TRIGGER
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER
PMU 1 CURR TRIGGER
PMU 1 ROCOF TRIGGER
SETTING
PMU 1 USER TRIGGER:
Off = 0
OR
FLEXLOGIC OPERAND
PMU 1 TRIGGERED
abs(P) > ACTIVE PICKUP
abs(P) > ACTIVE PICKUP
abs(P) > ACTIVE PICKUP
OR
abs(P) > 3*(ACTIVE PICKUP)
abs(Q) > REACTIVE PICKUP
abs(Q) > REACTIVE PICKUP
abs(Q) > REACTIVE PICKUP
abs(Q) > 3*(REACTIVE PICKUP)
S > APPARENT PICKUP
S > APPARENT PICKUP
S > APPARENT PICKUP
S > 3*(APPARENT PICKUP)
SETTINGS
PMU 1 SIGNAL SOURCE:
ACTIVE POWER, PA
ACTIVE POWER, PB
ACTIVE POWER, PC
3P ACTIVE POWER, P
REACTIVE POWER, QA
REACTIVE POWER, QB
REACTIVE POWER, QC
3P REACTIVE POWER, Q
APPARENT POWER, SA
APPARENT POWER, SB
APPARENT POWER, SC
3P APPARENT POWER, S
PMU 1 POWER TRIGGER REACTIVE:
PMU 1 POWER TRIGGER APPARENT:
to STAT bits of
the data frame
SETTINGS
PKP
t
0
PMU 1 POWER TRIGGER PKP TIME:
0
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...