![GE Multilin D400 Скачать руководство пользователя страница 81](http://html1.mh-extra.com/html/ge/multilin-d400/multilin-d400_hardware-user-manual_4042163081.webp)
CHAPTER 5: POWERING UP THE D400
POWER SUPPLY ALARMS
D400 SUBSTATION GATEWAY USER’S MANUAL
GENERAL
81
System fail alarm
The D400 includes a System Fail contact closure to provide an external indication of
system status. The System Fail alarm is also indicated by the CPU Ready LED on the front
panel of the main module turning off.
The indicator or audible alarm can be wired to operate as follows:
•
ON when system failure has occurred
•
ON when system is functioning properly
The System Fail contact closure provides three contacts (terminals 4, 5 and 6) on terminal
block
TB2
.
Contact closure rated for 0.1 A @ 300 V maximum.
To connect the
System Fail relay
1.
Remove the terminal block protective
plastic cover.
2.
Wire a lamp to terminals 4, 5 and 6 on terminal block
TB2
as follows:
For proper connection, the recommended tool torque settings for power terminal
screws are 10.8 in-lb [1.22 Nm].
3.
Replace the terminal block protective plastic cover.
Figure 50: System Fail Alarm Connection
To enable the indicator when system is…
Wire the lamp between…
Failed
Terminals 4 and 5
Functioning properly
Terminals 5 and 6
Light ON
after failure
Light ON
when operational
Station Battery / Power Source
Power
Fail
System
Fail
TB2
Содержание Multilin D400
Страница 10: ...10 GENERAL D400 SUBSTATION GATEWAY USER S MANUAL SAFETY WORDS AND DEFINITIONS ABOUT THIS DOCUMENT...
Страница 24: ...24 GENERAL D400 SUBSTATION GATEWAY USER S MANUAL STORAGE RECOMMENDATIONS CHAPTER 1 BEFORE YOU START...
Страница 30: ...30 GENERAL D400 SUBSTATION GATEWAY USER S MANUAL PHYSICAL INSTALLATION CHAPTER 2 INSTALLING THE D400...
Страница 90: ...90 GENERAL D400 SUBSTATION GATEWAY USER S MANUAL TESTING THE NETWORK CONNECTION CHAPTER 6 SETTING UP THE D400...
Страница 114: ...114 GENERAL D400 SUBSTATION GATEWAY USER S MANUAL COMPLIANCE STANDARDS APPENDIX A STANDARDS PROTECTION...
Страница 118: ...118 GENERAL D400 SUBSTATION GATEWAY USER S MANUAL ACRONYM DEFINITIONS APPENDIX B LIST OF ACRONYMS...
Страница 124: ...124 GENERAL D400 SUBSTATION GATEWAY USER S MANUAL...