
P446SV
Appendix B -Settings and Signals
P446SV-TM-EN-1
B177
ORDINAL
SIGNAL NAME
ELEMENT NAME
DESCRIPTION
854
Auto Close CB1
DDB_AUTO_CLOSE
This is a signal issued by the autoreclose logic to the general CB1 Control logic when the conditions to autoreclose CB1 are satisfied
(dead time complete, CB healthy etc).
855
CB2 AR 1p InProg
DDB_AR_1_POLE_IN_PROGRESS_2
Single pole auto-reclose in progress (dead time is running) CB2
858
AR Force CB1 3P
DDB_AR_FORCE_3_POLE_TRIPS
This DDB is set when the autoreclose logic has determined that single pole tripping/autoreclosing is not permitted for CB1. It can be
applied in PSL when required to force trip conversion logic for internal and/or external protection to three phase trip mode for CB1.
859
AR Blocked
DDB_AR_BLOCKED
It indicates that AR has been blocked (ex. from external input BAR)
860
CB1 LO Alarm
DDB_CB_LOCKOUT_ALARM
Composite Lockout Alarm - circuit breaker locked out due to auto-recloser, or condition monitioring
862
Block Contacts
DDB_CONTACTS_BLOCKED_IP
Input DDB signal used to drive IED to be contacts blocked
If the device has been put into 'Contact Blocked' mode using this input signal then the Apply Test command will not execute. This is to
prevent a device that has been blocked by an external process having its contacts operated by a local operator using the HMI.
If the Block Contacts DDB is not set and the Apply Test command in is issued, the contacts will change state.
863
Contacts Blocked
DDB_CONTACTS_BLOCKED_OP
Indicates contacts blocked mode enabled. Can be mapped in PSL and sent via InterMiCOM/IM64 to block contacts at the remote end.
864
IA< Start
DDB_PHASE_A_UNDERCURRENT
A phase undercurrent level detector pickup (detects low current). It is used for breaker failure in models with one CT input and also it
is used for fault record reset (as the sum CTs in models with two CTs)
865
IB< Start
DDB_PHASE_B_UNDERCURRENT
B phase undercurrent level detector pickup (detects low current). It is used for breaker failure in models with one CT input and also it
is used for fault record reset (as the sum CTs in models with two CTs)
866
IC< Start
DDB_PHASE_C_UNDERCURRENT
C phase undercurrent level detector pickup (detects low current). It is used for breaker failure in models with one CT input and also it
is used for fault record reset (as the sum CTs in models with two CTs)
867
CB1 IA< Start
DDB_PHASE_A_UNDERCURRENT_CB1
A phase undercurrent level detector pickup (detects low current in CT1). It is used for breaker failure in models with two CT inputs
868
CB1 IB< Start
DDB_PHASE_B_UNDERCURRENT_CB1
B phase undercurrent level detector pickup (detects low current in CT1). It is used for breaker failure in models with two CT inputs
869
CB1 IC< Start
DDB_PHASE_C_UNDERCURRENT_CB1
C phase undercurrent level detector pickup (detects low current in CT1). It is used for breaker failure in models with two CT inputs
870
CB2 IA< Start
DDB_PHASE_A_UNDERCURRENT_CB2
A phase undercurrent level detector pickup (detects low current in CT2). It is used for breaker failure in models with two CT inputs
871
CB2 IB< Start
DDB_PHASE_B_UNDERCURRENT_CB2
B phase undercurrent level detector pickup (detects low current in CT2). It is used for breaker failure in models with two CT inputs
872
CB2 IC< Start
DDB_PHASE_C_UNDERCURRENT_CB2
C phase undercurrent level detector pickup (detects low current in CT2). It is used for breaker failure in models with two CT inputs
873
ISEF< Start
DDB_SEF_UNDERCURRENT
SEF undercurrent level detector pickup (detects low current in CT SEF)
876
Z1X Active
DDB_ZONE1_EXT_ACTIVE
Zone 1 extension active - zone 1 is operating in its reach extended mode
877
TOC Active
DDB_TOC_ACTIVE
Trip on close functions (either SOTF or TOR) active. These elements are in-service for a period of time following circuit breaker closure
878
TOR Active
DDB_TOR_ACTIVE
Trip on re-close protection is active - indicated TOC delay timer has elapsed after circuit breaker opening, and remains in-service on
auto-reclosure for the duration of the trip on close window
879
SOTF Active
DDB_SOTF_ACTIVE
Switch on to fault protection is active - in service on manual breaker closure, and then remains in-service for the duration of the trip
on close window
880
SChksInactiveCB1
DDB_SYSCHECKS_INACTIVE
Output from CB1 system check logic: indicates system checks for CB1 are disabled (setting "System Checks CB1" = Disabled or global
setting "System Checks" = DiD2269
881
CB1 CS1 Enabled
DDB_CHECKSYNC_1_ENABLED
DDB input must be high to enable CB1check sync 1 logic to operate. Defaults to high if not mapped in PSL; if mapped in PSL must be
Содержание MiCOM P40 Agile
Страница 2: ......
Страница 24: ...Contents P446SV xxii P446SV TM EN 1 ...
Страница 33: ...CHAPTER 1 INTRODUCTION ...
Страница 34: ...Chapter 1 Introduction P446SV 2 P446SV TM EN 1 ...
Страница 46: ...Chapter 1 Introduction P446SV 14 P446SV TM EN 1 ...
Страница 47: ...CHAPTER 2 SAFETY INFORMATION ...
Страница 48: ...Chapter 2 Safety Information P446SV 16 P446SV TM EN 1 ...
Страница 60: ...Chapter 2 Safety Information P446SV 28 P446SV TM EN 1 ...
Страница 61: ...CHAPTER 3 HARDWARE DESIGN ...
Страница 62: ...Chapter 3 Hardware Design P446SV 30 P446SV TM EN 1 ...
Страница 88: ...Chapter 3 Hardware Design P446SV 56 P446SV TM EN 1 ...
Страница 89: ...CHAPTER 4 SOFTWARE DESIGN ...
Страница 90: ...Chapter 4 Software Design P446SV 58 P446SV TM EN 1 ...
Страница 101: ...CHAPTER 5 CONFIGURATION ...
Страница 102: ...Chapter 5 Configuration P446SV 70 P446SV TM EN 1 ...
Страница 124: ...Chapter 5 Configuration P446SV 92 P446SV TM EN 1 ...
Страница 125: ...CHAPTER 6 SAMPLED VALUE OPERATION ...
Страница 126: ...Chapter 6 Sampled Value Operation P446SV 94 P446SV TM EN 1 ...
Страница 136: ...Chapter 6 Sampled Value Operation P446SV 104 P446SV TM EN 1 ...
Страница 137: ...CHAPTER 7 DISTANCE PROTECTION ...
Страница 138: ...Chapter 7 Distance Protection P446SV 106 P446SV TM EN 1 ...
Страница 196: ...Chapter 7 Distance Protection P446SV 164 P446SV TM EN 1 ...
Страница 197: ...CHAPTER 8 CARRIER AIDED SCHEMES ...
Страница 198: ...Chapter 8 Carrier Aided Schemes P446SV 166 P446SV TM EN 1 ...
Страница 240: ...Chapter 8 Carrier Aided Schemes P446SV 208 P446SV TM EN 1 ...
Страница 241: ...CHAPTER 9 NON AIDED SCHEMES ...
Страница 242: ...Chapter 9 Non Aided Schemes P446SV 210 P446SV TM EN 1 ...
Страница 256: ...Chapter 9 Non Aided Schemes P446SV 224 P446SV TM EN 1 ...
Страница 257: ...CHAPTER 10 POWER SWING FUNCTIONS ...
Страница 258: ...Chapter 10 Power Swing Functions P446SV 226 P446SV TM EN 1 ...
Страница 281: ...CHAPTER 11 AUTORECLOSE ...
Страница 282: ...Chapter 11 Autoreclose P446SV 250 P446SV TM EN 1 ...
Страница 376: ...Chapter 11 Autoreclose P446SV 344 P446SV TM EN 1 ...
Страница 377: ...CHAPTER 12 CB FAIL PROTECTION ...
Страница 378: ...Chapter 12 CB Fail Protection P446SV 346 P446SV TM EN 1 ...
Страница 389: ...CHAPTER 13 CURRENT PROTECTION FUNCTIONS ...
Страница 390: ...Chapter 13 Current Protection Functions P446SV 358 P446SV TM EN 1 ...
Страница 416: ...Chapter 13 Current Protection Functions P446SV 384 P446SV TM EN 1 ...
Страница 417: ...CHAPTER 14 VOLTAGE PROTECTION FUNCTIONS ...
Страница 418: ...Chapter 14 Voltage Protection Functions P446SV 386 P446SV TM EN 1 ...
Страница 431: ...CHAPTER 15 FREQUENCY PROTECTION FUNCTIONS ...
Страница 432: ...Chapter 15 Frequency Protection Functions P446SV 400 P446SV TM EN 1 ...
Страница 438: ...Chapter 15 Frequency Protection Functions P446SV 406 P446SV TM EN 1 ...
Страница 439: ...CHAPTER 16 MONITORING AND CONTROL ...
Страница 440: ...Chapter 16 Monitoring and Control P446SV 408 P446SV TM EN 1 ...
Страница 476: ...Chapter 16 Monitoring and Control P446SV 444 P446SV TM EN 1 ...
Страница 477: ...CHAPTER 17 SUPERVISION ...
Страница 478: ...Chapter 17 Supervision P446SV 446 P446SV TM EN 1 ...
Страница 490: ...Chapter 17 Supervision P446SV 458 P446SV TM EN 1 ...
Страница 491: ...CHAPTER 18 DIGITAL I O AND PSL CONFIGURATION ...
Страница 492: ...Chapter 18 Digital I O and PSL Configuration P446SV 460 P446SV TM EN 1 ...
Страница 504: ...Chapter 18 Digital I O and PSL Configuration P446SV 472 P446SV TM EN 1 ...
Страница 505: ...CHAPTER 19 FIBRE TELEPROTECTION ...
Страница 506: ...Chapter 19 Fibre Teleprotection P446SV 474 P446SV TM EN 1 ...
Страница 522: ...Chapter 19 Fibre Teleprotection P446SV 490 P446SV TM EN 1 ...
Страница 523: ...CHAPTER 20 ELECTRICAL TELEPROTECTION ...
Страница 524: ...Chapter 20 Electrical Teleprotection P446SV 492 P446SV TM EN 1 ...
Страница 534: ...Chapter 20 Electrical Teleprotection P446SV 502 P446SV TM EN 1 ...
Страница 535: ...CHAPTER 21 COMMUNICATIONS ...
Страница 536: ...Chapter 21 Communications P446SV 504 P446SV TM EN 1 ...
Страница 606: ...Chapter 21 Communications P446SV 574 P446SV TM EN 1 ...
Страница 607: ...CHAPTER 22 CYBER SECURITY ...
Страница 608: ...Chapter 22 Cyber Security P446SV 576 P446SV TM EN 1 ...
Страница 625: ...CHAPTER 23 INSTALLATION ...
Страница 626: ...Chapter 23 Installation P446SV 594 P446SV TM EN 1 ...
Страница 637: ...CHAPTER 24 COMMISSIONING INSTRUCTIONS ...
Страница 638: ...Chapter 24 Commissioning Instructions P446SV 606 P446SV TM EN 1 ...
Страница 695: ...CHAPTER 25 MAINTENANCE AND TROUBLESHOOTING ...
Страница 696: ...Chapter 25 Maintenance and Troubleshooting P446SV 664 P446SV TM EN 1 ...
Страница 712: ...Chapter 25 Maintenance and Troubleshooting P446SV 680 P446SV TM EN 1 ...
Страница 713: ...CHAPTER 26 TECHNICAL SPECIFICATIONS ...
Страница 714: ...Chapter 26 Technical Specifications P446SV 682 P446SV TM EN 1 ...
Страница 741: ...APPENDIX A ORDERING OPTIONS ...
Страница 742: ...Appendix A Ordering Options P446SV P446SV TM EN 1 ...
Страница 744: ...Appendix A Ordering Options P446SV A2 P446SV TM EN 1 ...
Страница 745: ...APPENDIX B SETTINGS AND SIGNALS ...
Страница 746: ...Appendix B Settings and Signals P446SV P446SV TM EN 1 ...
Страница 954: ...Appendix B Settings and Signals P446SV B208 P446SV TM EN 1 ...
Страница 955: ...APPENDIX C WIRING DIAGRAMS ...
Страница 956: ...Appendix C Wiring Diagrams P446SV P446SV TM EN 1 ...
Страница 960: ......
Страница 961: ......