1-
2
MDP Digital Time Overcurrent Relay
GE Power Management
1 INTRODUCTION
GEK-100682D
1
Figure 1–1: SINGLE-LINE DIAGRAM
1.2 ORDER CODES
MDP
S
S
S
S
S
0
No communications or control inputs
(Block Ground, Block Instantaneous, Breaker Status)
1
Control Inputs and communications upgrade socket
2
CommNet
3
Modbus RTU
4
RS232
5
RS485
1
5 A nominal, 0.5 to 4.375 A ground, 1.5 to 13.125 A phase
2
5 A nominal, 1.5 to 13.125 A ground, 1.5 to 13.125 A phase
3
5 A nominal, 0.1 to 0.875 A ground, 1.5 to 13.125 A phase
4
1 A nominal, 0.1 to 0.875 A ground, 0.3 to 2.625 A phase
5
1 A nominal, 0.3 to 2.625 A ground, 0.3 to 2.625 A phase
6
1 A nominal, 0.05 to 0.4375 A ground, 0.3 to 2.625 A phase
7
5 A nominal, 0.5 to 4.375 A ground and phase
1
24 to 48 V DC
2
48 to 125 V DC, 35 to 120 V AC
3
110 to 250 V DC, 85 to 240 V AC
00000
Reserved
D
Revision Level
707750A1.CDR
BUS 1
TRANSFORMER 1
FEEDER
NO. 1
FEEDER
NO. 3
FEEDER
NO. 2
50/51
50/51
50/51