7-
4
MDP Digital Time Overcurrent Relay
GE Power Management
7 MODBUS PROTOCOL
GEK-100682D
7
1011
Phase A trip current
0 to 10 A (5 A relay)
0 to 2 A (1 A relay)
RO
Float
2
80/74/09-0Ah
1013
Phase B trip current
0 to 10 A (5 A relay)
0 to 2 A (1 A relay)
RO
Float
2
80/74/0B-0Ch
1015
Phase C trip current
0 to 10 A (5 A relay)
0 to 2 A (1 A relay)
RO Float
2
80/74/0D-0Eh
1017
Ground trip current
0 to 3 A (5 A relay)
0 to 0.7 A (1 A relay)
RO
Float
2
80/74/0F-10h
1019
Trip time
0 to 999.99 sec.
RO
Float
2
80/74/11-14h
1021
Breaker Status
00 to 01h
RO
Unsigned Integer
00h: Closed, 01h: Open
1
80/57/00h
1022
Relay Hardware Status
00 to 04h
RO
Unsigned Integer
00h: Relay is OK
01h: Relay not responding to read
02h: Relay not responding to write
03h: Command error reported
04h: Fatal error in Relay
1
80/57/03h
COMMNET COMMUNICATION STATISTICS REGISTERS
1500
Device Status
N/A
RO
1 = ALIVE, 0 = DEAD
1
N/A
1501
Total Communication errors
N/A
RO
Unsigned Integer
1
N/A
1502
CRC Errors
N/A
RO
Unsigned Integer
1
N/A
1503
Transmit Failures
N/A
RO
Unsigned Integer
1
N/A
1504
Receive Time-out
N/A
RO
Unsigned Integer
1
N/A
1505
Receive Errors
N/A
RO
Unsigned Integer
1
N/A
EVENT REGISTERS
2000
Event Code - EVENT 1
0 to 256
RO
Unsigned Integer
1
2001
Hour
0 to 23 hrs.
RO
Unsigned Integer
1
2002
Minute
0 to 59 min.
RO
Unsigned Integer
1
2003
Seconds
0 to 59 sec.
RO
Unsigned Integer
1
2004
Milliseconds
msecs
RO
Unsigned Integer
1
2005
Event specific data 1
1
2006
Event specific data 2
1
2007
Event specific data 3
1
2008
Event specific data 4
1
2009
Event specific data 5
1
2010
Event specific data 6
1
2011
Event code - EVENT 2
0 to 256
RO
Unsigned Integer
1
2012
Hour
0 to 23 hrs.
RO
Unsigned Integer
1
2013
Minute
0 to 59 min.
RO
Unsigned Integer
1
2014
Seconds
0 to 59 sec.
RO
Unsigned Integer
1
2015
Milliseconds
msecs
RO
Unsigned Integer
1
Table 7–1: MODBUS MEMORY MAP (Sheet 2 of 4)
REGISTER CONTENTS
RANGE
TYPE
R/W
FORMAT CODE
BYTES
COMMNET
COMMAND
Содержание MDP
Страница 2: ...Courtesy of NationalSwitchgear com ...