Masoneilan 4700P/E & 4800P/E Positioners Manual
=
|
17
© 2015 General Electric Company. All rights reserved
.
WARNING
When a valve (because of high pressure drop) uses a supply
pressure higher than 20 psig, the 3-15 psig instrument signal may
not be sufficient to operate the valve when the positioner is
bypassed. Moreover, if the positioner with a high supply pressure
is bypassed suddenly, the high pressure in the actuator may
damage the diaphragm and/or the control instrument. Therefore,
the bypass valve should be used only if the positioner supply
pressure is 20 psig (140 kPa or 1, 4 bar), or at most 35 psig (240
kPa, or 2, 4 bar), or if the controller is capable of operating the
valve directly. When bypassing a positioner, ensure that the
controller output is equal to supply required to operate valve.
Содержание Masoneilan 4700P
Страница 4: ...This page intentionally left blank...
Страница 8: ...This page intentionally left blank...
Страница 10: ...This page intentionally left blank...
Страница 14: ...This page intentionally left blank...
Страница 18: ...This page intentionally left blank...
Страница 40: ...2015 General Electric Company All rights reserved 40 GE Oil Gas Figure 13 FM Installation...
Страница 42: ...2015 General Electric Company All rights reserved 42 GE Oil Gas Figure 15 ATEX Installation...
Страница 46: ...This page intentionally left blank...
Страница 66: ...2015 General Electric Company All rights reserved 66 GE Oil Gas...
Страница 67: ...Masoneilan 4700P E 4800P E Positioners Manual 67 2015 General Electric Company All rights reserved...
Страница 74: ...2015 General Electric Company All rights reserved 74 GE Oil Gas Figure 21 Bypass Option 4700 Only...
Страница 78: ...This page intentionally left blank...
Страница 79: ......