Masoneilan 4700P/E & 4800P/E Positioners Manual
=
|
19
© 2015 General Electric Company. All rights reserved
.
Mounting and Orientation
The valve is installed in the pipeline to operate in one of two ways:
Air to Open
Air to Close
Close on air failure
Open on air failure
(Reverse Action)
(Direct Action)
The choice depends on the desired air failure action. This subject is dealt with in separate actu-
ator instructions. The positioner can operate either by direct action (increasing instrument signal
produces an increase in output pressure) or reverse action (increasing instrument signal produc-
es a decrease in output pressure). See Figure 3 and Figure 4.
The 4700E/4800E is not available with reverse action, hence
if the application demands reverse action, a 4700P/4800P
with an external I/P Transducer is required.
NOTE
Installation
Содержание Masoneilan 4700E
Страница 4: ...This page intentionally left blank ...
Страница 8: ...This page intentionally left blank ...
Страница 10: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 18: ...This page intentionally left blank ...
Страница 40: ... 2015 General Electric Company All rights reserved 40 GE Oil Gas Figure 13 FM Installation ...
Страница 42: ... 2015 General Electric Company All rights reserved 42 GE Oil Gas Figure 15 ATEX Installation ...
Страница 46: ...This page intentionally left blank ...
Страница 66: ... 2015 General Electric Company All rights reserved 66 GE Oil Gas ...
Страница 67: ...Masoneilan 4700P E 4800P E Positioners Manual 67 2015 General Electric Company All rights reserved ...
Страница 74: ... 2015 General Electric Company All rights reserved 74 GE Oil Gas Figure 21 Bypass Option 4700 Only ...
Страница 78: ...This page intentionally left blank ...
Страница 79: ......