Power Redundancy

The terminology for power sources, supplies, and converters is often confused. An external power source is provided for the
electronics, which have internal power supplies that convert the source voltage to low-level regulated busses for circuit
boards. In many cases, there is also a wetting voltage required for contact inputs, analog inputs, and power feeds for field
solenoids that are powered from the control.

The control system accepts one, or redundant, 24 V dc, 125 V dc, and 115/230 V ac sources that can be mixed in any
combination. Internal power supplies convert the source voltage to 28 V dc for the controller, IONet switches, and the
distributed I/O modules. Internal supplies are normally non-redundant for simplex control systems, but can be provided as
dual redundant, if required. Dual redundant power supplies are provided for dual redundant control systems, and dual/triple
redundant power supplies are provided for triple redundant controls systems. An exception is remote I/O panels with
non-critical I/O. These panels normally have a single power supply regardless of whether the controllers are redundant or
non-redundant. But, they can be supplied in redundant pairs too, if required. Additional redundancy options are available.

Internal Power Converters Create 28V dc for:

- Controllers

- IONET Switches

- I/O Modules

Field Power Sources

- 1 Source

- 2 Sources

- 3 Sources

24V dc

125V dc

115 /230V ac

28V dc

Controllers

Switches

I/O Modules

Power for Electronics

Field Power Sources

- 1 Source

- 2 Sources

- 3 Sources

24V dc

48V dc

125 V dc

Wetting Voltage

Contact Inputs

Transducers

Solenoids

Power for Field Devices

115/230 V ac

Wetting Voltage 
from Field

Redundant Supplies

AC to 24Vdc

Redundant Supplies

AC to 28Vdc

Diode High-Selects

Power Sources, Converters, and Supplies

Different power sources can be provided for the internal electronics and the wetting voltage for contact inputs, transducers,
and solenoid power. For example, redundant 230 V ac sources can be converted to 28 V dc for the internal electronics. If 125
V dc wetting voltage is needed for contact inputs or field solenoids, it can be provided directly from the station battery or
from redundant 230 V ac to 125 V dc converters in the control.

Diagnostics monitor power sources and power supplies for fault detection and to enable online repair.

6

GEI-100728A

Mark VIe Controls System Redundancy Options

Public Information

Содержание Mark VIe

Страница 1: ...nt contains non sensitive information approved for public disclosure GE may have patents or pending patent applications covering subject matter in this document The furnishing of this document does no...

Страница 2: ...Controller 7 5 I O Network Redundancy 7 6 I O Redundancy 8 6 1 Dual Redundancy 8 6 2 Triple Modular Redundancy 11 7 Tripping Reliability 15 8 Digital Bus Reliability 17 8 1 FOUNDATION Fieldbus 17 8 2...

Страница 3: ...ting the process Field components for example sensors actuators and wiring cause over half of forced outages Therefore redundancy of field components is an important consideration in the overall contr...

Страница 4: ...one component is out voted by the other two In the case of three lube oil pressure switches the protective system performs a simple logical vote with no need to predict in advance a probable failure m...

Страница 5: ...ing Blocks Controller 3 IONET Ports 2 Control Network Ports 1 COM Port IONET Switch I O Module I O Pack Local Processor Data Acquisition Terminal Block Typical Mark VIe Architecture Instruction Guide...

Страница 6: ...ther the controllers are redundant or non redundant But they can be supplied in redundant pairs too if required Additional redundancy options are available Internal Power Converters Create 28V dc for...

Страница 7: ...board rack or mounted inside the rack with communication on the backplane The I O network consists of active electronics at both ends and multiple failure modes so its redundancy is just as important...

Страница 8: ...at the I O pack level Therefore replacement of I O has minimal impact on monitoring and control of the overall control system An extension of this is to add a third sensor whose value can be voted in...

Страница 9: ...ovides recovery data 4 Receives external commands 5 Creates process alarms Data outputs from dual redundant controllers are normally implemented with each controller sending its signal to its switch a...

Страница 10: ...ollers IONET switches and Ethernet ports on a common I O pack which controls a relay driver and a relay Level 2 also provides dual redundant controllers and IONET switches but extends the redundancy t...

Страница 11: ...ed or transmitted individually Fanned inputs are transmitted on the IONET with three I O packs on the I O module Therefore a failure of an I O pack does not inhibit any controller from seeing all of t...

Страница 12: ...les 3 Less IONET switches Non critical data that is being used for non essential monitoring is usually implemented without redundancy Redundant and non redundant I O coexists in most control systems T...

Страница 13: ...nt sharing circuit Analog Voting occurs with a3 coil servo Extended Voting at Field Device Example 3 Coil Servo Valve Actuator Typical nuclear configuration Valve Regulator Valve Ref Valve Regulator V...

Страница 14: ...Requirements for no single point failures must be evaluated on a case by case basis to determine the best way to approach this from the system level The preceding figure displays a variation of outpu...

Страница 15: ...responding I O control protect and monitor the turbine Primary protection includes a full set of all trip functions and backup protection includes a small subset of the protection functions to backup...

Страница 16: ...control valves and de energize the trip solenoids from the primary side Another example the backup protection monitors communications from each controller so it can be configured to initiate a trip o...

Страница 17: ...the designated controller and a secondary controller Therefore the primary linking device is the one connected to the primary controller Less common are applications with a single controller and redun...

Страница 18: ...al Controllers Supplies Switches Simplex Non redundant Dual with Redundant I O Full Triple Redundant Dual Redundant Triple Relative Contributions to Reliability and MTBFO Adding redundancy to the elec...

Страница 19: ...Public Information...

Отзывы: